Toshiba Strata DK 280 Installation Manual page 649

Digital business telephone system
Hide thumbs Also See for Strata DK 280:
Table of Contents

Advertisement

2.
Verify the power supply ON/OFF
switch is in the
ON position.
Note:
The base cabinet ON/OFF switch must be ON
to allow expansion
cabinet power supplies
to
operate.
Verify that the data ribbon cable is plugged
into
the base from all expansion
cabinets.
3.
Ensure
the AC power
cord is plugged
into the
RPSU280
AC IN connector
and the commercial
AC outlet
(or power
strip (RPSB) if used).
The
green POWER LED indicator will be on when AC
power
is connected
to the RPSU280
and the
power
supply
ON/OFF
switch
is ON.
Take
appropriate
action
to restore
AC power
if
necessary.
Note:
The green
power
LED indicates
that AC
voltage is present at the AC IN connector
only
when the RPSU280
ON/OFF switch ON. This
is helpful
for battery
backup
systems-the
POWER
indicator
will be OFF and the +5V
and -5V
indicators
will be ON when
the
DK280
is operating
on
reserve
power
(batteries).
4.
Verify that the +5V and -5V green LED indicators
are ON. If one or both indicators are OFF, remove
cabinet
PCBs one at a time and check if +5V or
-5V indicators turn on (it may be necessary to turn
power OFF and ON to restore &5 volts). Replace
defective
PCBs causing &5 volt fault.
IMPORTANT!
If a CRCU PCB is installed on an RCTU PCB,
25 volts will turn off. Do not install CRCU on
RCTU.
Only
RRCS
DTMF
PCBs
can be
installed on RCTU.
5.
Lightly press the three -24V
circuit breakers
to
ensure they have not accidentally
opened
during
shipment.
If a circuit breaker
continues
to "trip,"
remove cabinet
PCBs, one at a time, and try to
reset the circuit breaker.
Replace defective
PCBs
if causing
-24
volt fault.
See the 24V circuit
breaker
assignments
in Figure
12-2 below.
If
breakers continue to trip, go to Step 7.
6.
Using a DC voltmeter,
measure
the power supply
DC output voltages at the "DC OUT" connector
on
the RPSU280.
Refer to Figure 12-2 for voltage pin
7.
8.
locations
and specifications.
Place the positive
(black) meter
lead on the FG screw.
Insert the
negative
(red) meter
lead tip into the DC out
connector
until it makes contact.
Make sure that +5 volt, -5 volts, and -24 volts are
within the range specified in Figure 12-2. Do this
test with PCBs inserted; if a voltage(s)
is not within
specification,
remove
PCBs, one at a time and
recheck
the
voltage.
(Power
may have to be
turned OFF and ON to restore a voltage.)
Replace
any PCB which causes a voltage fault. If voltage
tests out of specification
with all PCBs removed
from the cabinet, go to Step 7.
Unplug the cabinet DC power connector
from the
RPSU280
"DC OUT" jack. Attempt
to reset -24
volt breakers
per Step 5. If breaker
cannot
be
reset replace power supply; if breakers reset go to
Step 8.
Check the power supply DC voltages
measuring
at the DK280 "DC OUT" jack with the black meter
lead on the BATT "+" terminal.
If the DC voltages
are within
specification
when
the cabinet
DC
power connector
is disconnected
but not within
specification
when the cabinet
is connected,
the
cabinet is probably defective.
If the DC voltages
are not within
specification
when
the
cabinet
DC power
connector
is
unplugged,
the RPSU280
power supply probably
is defective.
Replace
the defective
cabinet
or
RPSU280
power supply per Chapter
3-Cabinet
Installation.
I
+5 Volts (white wire) cannot be checked
with
IMPORTANT!
the DC out cable disconnected.
9.
Using the DC voltmeter,
check
the RPSU280
battery
charger
as follows:
Remove
the battery
cable from the power supply "BATT" connector.
Place the positive
(black) meter
lead on the "+"
BATT pin and the negative (red) meter lead on the
'I-" BATT pin. The allowed range is (-26.3
volts -
-27.8
volts).
If BATT
output
is not
within
specification,
replace the RPSU280.
January
1996
12-3

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents