Toshiba Strata DK 280 Installation Manual page 681

Digital business telephone system
Hide thumbs Also See for Strata DK 280:
Table of Contents

Advertisement

Table
13-5
Program
91-l
-
Automatic
PCB Recognition/Port
Renumber
Step
Action
Display/Printout
1
Enter Program
Mode
>MODE PROG
At the
>MODE
prompt, type
PROG,
press
Enter.
2
Enter Program
Number
91
P 91
Press
Enter.
P91
3
Type 1.
P 91
P91 1
4
Type button / LED number
0 1.
P 91
P91 1 01 N
5
Change
LED 01 to "ON" by typing
Y.
P 91
P91 1 01 N Y
6
Press
the
Spacebar
once.
P 91
P91
1 01 N Y
02
N
Y
7
Change
LED 02 to "ON" by typing
Y.
P
91
Note:
P91 1 01 N Y
/f data is not entered correct/y, press Delete
+ Enter
02N
Y
at the same time to return to Step 3.
8
Press
ENTER
twice.
DK CONNECT
You will exit the programming
mode after you press
Enter
the
>CODE
second time.
CAUTION
!
Running
this program
will drop all calls, including
the remote
maintenance
CO line. The remote
maintenance
communication
path
between
the remote
terminal/modem
and the DK280
remote
maintenance
modem must be reestablished
to continue remote maintenance.
This will not be possible if
the DK280 RMDS or IMDU is used unless the RMDS or IMDU is enabled in Program 77-l (LED 14 ON)
from the on-site programming
station (205) after running Program 9 I- 1.
13-l
8
January
1996