MERLIN LEGEND Communications System Release 5.0
Installation 555-650-140
Installing the Control Unit
AC Power and Grounding
uxiliary equipment requires additional AC outlets.
A
If a printer or PC is installed on the system, it must be plugged into the
same AC branch as the power supply of the basic carrier.
If the printer or PC is 50 ft. (15 m) or more from the control unit, or is
plugged into a different AC circuit, Asynchronous Data Units (ADUs)
must be installed as well.
includes complete installation instructions.
The AC power requirements indicated in "AC Outlet Tests," on page 2-8,
must be met.
From AC
Load Center
(2 separately
fused 15 A
circuits)
HUBBELL
Receptacles
(5262 15 A
or equivalent)
Single-Point
Ground
Figure 2-1.
AC Grounding Requirements
Chapter 5, ''Installing the PC, CAT, or
Ground Wire
#14 AWG
Ground Bar Mounted
on a 4" Box (Square
"D" PK9GTA or
approved equivalent)
#12 or #14 AWG Copper
Wire to Each Power Supply
Grounding Screw
4" Box (RACO 230
or equivalent)
4" Cover
(RACO 807
or equivalent)
Ground Wire
#6 AWG Copper
Approved
Building Ground
Issue 1
June 1997
Page 2-7
Printer'',