General Grounding Requirements; Grounding Impedance Requirements; Lightning Rod Requirements; Feeder Cabling And Grounding Requirements - Huawei BBU3806 Installation Manual

Wcdma base band unit
Table of Contents

Advertisement

Installation Manual – Hardware Installation
BBU3806 WCDMA Base Band Unit
Tower
ground grid

Figure 3-1 Ground grid

Ground the cabling rack, suspend iron rack, NodeB rack or frame, metal air duct,
and metal doors and windows in the equipment room.

3.4.6 General Grounding Requirements

To meet general grounding requirements, you shall:
Never connect the neutral line of AC power cable to the protection ground of any
exchange or communications devices.
Make all ground cables as short and straight as possible.
Never add fuse or switch to ground cables.
Make sure that there is no oxidation on the grounding bar against large contact
impedance between ground cables and grounding bar.
Ensure that ground cables connect to the protection grounding bar of the
equipment room securely.

3.4.7 Grounding Impedance Requirements

The grounding impedance of NodeB cannot exceed 5 ohm. For places with less than
20 thunderstorm days in a year, the grounding impedance of NodeB can be lower
than 10 ohm.

3.4.8 Lightning Rod Requirements

Make sure that all NodeB antennas stay under effective protection of the lightning rod.
The lightning rod must have a dedicated line for lightning current lead. The lightning
rod shall be made of 40 mm × 4 mm galvanized flat steel.

3.4.9 Feeder Cabling and Grounding Requirements

To meet the requirements for feeder cabling and grounding, you shall:
Horizontal
grounding body
Equipment room
ground grid
Huawei Technologies Proprietary
BBU3806 Operating Environment Requirements
Vertical
grounding body
Transformer
ground grid