8.4

Preparing the Flash File System

Pos : 67.26.2 /Serie 750 ( WAGO-I/O- SYST EM)/In Betri eb nehmen/F eldbus knoten in Betri eb nehmen/Fl ash-D ateis ystem vor ber eiten - Einl eitung ( Koppler) @ 5\mod_1244641312485_21.doc x @ 35228 @ @ 1
The flash file system must be prepared in order to use the Web interface of the
fieldbus coupler to make all configurations.
The flash file system is already prepared when delivered.
However, if the flash file system has not been initialized on your fieldbus coupler
or it has been destroyed due to an error, you first must initialize it manually to
access it.
Pos : 67.26.3 /Serie 750 ( WAGO-I/O- SYST EM)/In Betri eb nehmen/F eldbus knoten in Betri eb nehmen/Hinweis: Kommuni kati ons kabel 750-920 nic ht unter Spannung s tec ken! (Koppler/C ontroll er) @ 4\mod_1239172916562_21.doc x @ 30343 @ @ 1
Do not connect Communication Cable when energized!
To prevent damage to the service interface, do not connect or disconnect 750-
920 respectively 750-923 Communication Cable when energized! The fieldbus
coupler/controller must be de-energized!
Pos : 67.26.4 /Serie 750 ( WAGO-I/O- SYST EM)/In Betri eb nehmen/F eldbus knoten in Betri eb nehmen/Hinweis: Daten werden durc h Z urüc ksetz en g elös cht! @ 5\mod_1244641489071_21.doc x @ 35235 @ @ 1
Resetting erases data!
Note that resetting erases all data and configurations.
Only use this function when the flash file system has not been initialized yet or
has been destroyed due to an error.
Pos : 67.26.5 /Serie 750 ( WAGO-I/O- SYST EM)/In Betri eb nehmen/F eldbus knoten in Betri eb nehmen/Betri ebsspg aussc hal ten, Kommuni kations kabel anschli eß en, Bertriebss pg an (Koppler) Schritt 1-3 @ 8\mod_1275650099297_21.doc x @ 57383 @ @ 1
1.
Switch off the supply voltage of the fieldbus coupler.
2.
Connect the communication cable 750-920 or 750-923 respectively the
Bluetooth
and to your computer.
3.
Switch on the supply voltage of the fieldbus coupler.
Pos : 67.26.6 /Serie 750 ( WAGO-I/O- SYST EM)/In Betri eb nehmen/F eldbus knoten in Betri eb nehmen/H ochl auf und LEDs (Koppl er) @ 4\mod_1243590574487_21.doc x @ 34500 @ @ 1
The fieldbus coupler is initialized. The coupler determines the I/O module
configuration and creates a process image.
During start-up, the I/O LED (red) flashes.
If the I/O LED lights up green after a brief period, the fieldbus coupler is
operational.
Pos : 67.26.7 /Serie 750 ( WAGO-I/O- SYST EM)/In Betri eb nehmen/F eldbus knoten in Betri eb nehmen/H ochl auf und LEDs - F ehler allgemei n, Hi nweis: Signalisierung/Bli nkc ode-Aus w. @ 4\mod_1243594306433_21.doc x @ 34538 @ @ 1
If an error occurs during start-up indicated by the I/O LED flashing red, evaluate
the error code and argument and resolve the error.
More information about LED signaling
The exact description for evaluating the LED signal displayed is available in the
section "Diagnostics" > ... > "LED Signaling".
Pos : 67.26.8 /Serie 750 ( WAGO-I/O- SYST EM)/In Betri eb nehmen/F eldbus knoten in Betri eb nehmen/Fl ash-D ateis ystem vor ber eiten, ETH ERNET-Setti ngs starten, Dateis ystem z urüc ksetzen Sc hritt 4-6 @ 5\mod_1244643184660_21.doc x @ 35238 @ @ 1
Start the "WAGO Ethernet Settings" program.
4.
®
Adapter 750-921 to the service interface of the fieldbus coupler
Commissioning