Configuration Registers; Table 127: Register Address 0X1022; Table 128: Register Address 0X1023; Table 129: Register Address 0X1024 - WAGO -I/O-SYSTEM 750 XTR Manual

Fc ethernet g3 xtr fieldbus coupler ethernet; 3rd generation; extreme
Hide thumbs Also See for WAGO-I/O-SYSTEM 750 XTR:
Table of Contents

Advertisement

178 Fieldbus Communication
Pos : 94.39 /Serie 750 ( WAGO-I/O-SYST EM)/Funkti onsbesc hrei bung/F eldbus kommuni kation/M ODBU S/Z ugriff auf R egister werte - Konfigurationsregister 0x1022 bis 0x1025 @ 3\mod_1235461775390_21.doc x @ 27632 @ 4 @ 1
11.2.5.5

Configuration Registers

The following registers contain configuration information of the connected
modules:

Table 127: Register Address 0x1022

Register address 0x1022 (4130
Value
Access
Description

Table 128: Register Address 0x1023

Register address 0x1023 (4131
Value
Access
Description

Table 129: Register Address 0x1024

Register address 0x1024 (4132
Value
Access
Description

Table 130: Register Address 0x1025

Register address 0x1025 (4133
Value
Access
Description
Pos : 94.40 /Serie 750 ( WAGO-I/O-SYST EM)/Funkti onsbesc hrei bung/F eldbus kommuni kation/M ODBU S/Z ugriff auf R egister werte - Konfigurationsregister 0x1028 ( x41) @ 4\mod_1235635808625_21.doc x @ 27808 @ @ 1

Table 131: Register Address 0x1028

Register address 0x1028 (4136
Value
Access
Description
Pos : 94.41 /Serie 750 ( WAGO-I/O-SYST EM)/Funkti onsbesc hrei bung/F eldbus kommuni kation/M ODBU S/Z ugriff auf R egister werte - Konfigurationsregister 0x1029 ( x41) @ 4\mod_1235635910031_21.doc x @ 27811 @ @ 1
Manual
Version 1.3.0
)
dec
CnfLen.AnalogOut
Read
Number of word-based outputs registers in the process image in bits (divide by 16
to get the total number of analog words)
)
dec
CnfLen.AnalogInp
Read
Number of word-based inputs registers in the process image in bits (divide by 16
to get the total number of analog words)
)
dec
CnfLen.DigitalOut
Read
Number of digital output bits in the process image
)
dec
CnfLen.DigitalInp
Read
Number of digital input bits in the process image
)
dec
Boot options
Read/write
Boot configuration:
1: BootP
2: DHCP
3: BootP-Request before static IP
4: EEPROM
WAGO-I/O-SYSTEM 750 XTR