Table 50: Blink Code Table For The 'I/O' Led Signaling, Error Code 4; Table 51: Blink Code Table For The 'I/O' Led Signaling, Error Code 5 - WAGO -I/O-SYSTEM 750 XTR Manual

Fc ethernet g3 xtr fieldbus coupler ethernet; 3rd generation; extreme
Hide thumbs Also See for WAGO-I/O-SYSTEM 750 XTR:
Table of Contents

Advertisement

WAGO-I/O-SYSTEM 750 XTR
750-352/040-000 FC ETHERNET G3 XTR

Table 50: Blink Code Table for the 'I/O' LED Signaling, Error Code 4

Error code 4: "Physical error, internal bus"
Error
Argument
-
n*
* The number of light pulses (n) indicates the position of the I/O module.
I/O modules without data are not counted (e.g., supply modules without diagnostics)

Table 51: Blink Code Table for the 'I/O' LED Signaling, Error Code 5

Error code 5: "Initialization error, internal bus"
Error
Argument
n*
* The number of light pulses (n) indicates the position of the I/O module.
I/O modules without data are not counted (e.g., supply modules without diagnostics)
Pos : 73.12 /Serie 750 ( WAGO-I/O-SYST EM)/Diagnos e/F eldbus koppler/-c ontroll er/Bli nkc ode-Tabellen - F ehl erc ode 6 ( 750-0352) @ 8\mod_1280140255621_21.doc x @ 61156 @ @ 1
Error Description
Solution
1.
2.
3.
4.
--- Is no error argument indicated by the I/O LED? ---
5.
--- Is an error argument indicated by the I/O LED? ---
5.
6.
Local bus data
7.
transmission error or
8.
interruption of the
local bus at the
fieldbus coupler
9.
10. Repeat the procedure described in step 6 while halving
11. Replace the faulty I/O module.
12. If there is only one I/O module on the fieldbus coupler and
Interruption of the
1.
local bus behind the
2.
nth bus module with
3.
process data
Error Description
Solution
Error in register
1.
communication
2.
during local bus
3.
initialization
Turn off the power supply to the node.
Plug in an end module behind the fieldbus coupler.
Turn the power supply on.
Observe the error argument signaled.
Replace the fieldbus coupler.
Identify the faulty I/O module by turning off the power
supply.
Plug the end module into the middle of the node.
Turn the power supply on again.
--- LED continues to flash? ---
Turn off the power and plug the end module into the
middle of the first half of the node (toward the fieldbus
coupler).
--- LED not flashing? ---
Turn off the power and plug the end module into the
middle of the second half of the node (away from the
fieldbus coupler).
Turn the power supply on again.
the step size until the faulty I/O module is detected.
the LED is flashing, either the I/O module or fieldbus
coupler is defective. Replace the defective component.
Turn off the power supply to the node.
Replace the (n+1) I/O module containing process data.
Turn the power supply on.
Turn off the power supply to the node.
Replace the (n+1) I/O module containing process data.
Turn the power supply on.
Diagnostics 135
Manual
Version 1.3.0