750-352/040-000 FC ETHERNET G3 XTR
Register Access Writing (with FC6 and FC16)

Table 107: Register Access Writing (with FC6 and FC16)

MODBUS address
[dec]
0...255
256...511
512...767
768...4095
4096...12287
12288...24575 0x3000...0x5FFF
24576...25339 0x6000...0x62FB
25340...28671 0x62FC...0x6FFF
28672...29435 0x7000...0x72FB
29436...65535 0x72FC...0xFFFF
Pos : 94.21 /Serie 750 ( WAGO-I/O-SYST EM)/Funkti onsbesc hrei bung/F eldbus kommuni kation/M ODBU S/MOD BU S-Register-Mappi ng - Abs atz C oil-Dienste, Bitz ugriffe @ 3\mod_1235393917265_21.doc x @ 27584 @ @ 1
The digital MODBUS services (coil services) are bit accesses, with which only the
states of digital I/O modules can be determined or changed. Complex I/O
modules are not attainable with these services and so they are ignored. Because
of this the addressing of the digital channels begins again with 0, so that the
MODBUS address is always identical to the channel number, (i.e. the digital input
no. 47 has the MODBUS address "46").
Pos : 94.22 /D okumentati on allgemei n/Gli ederungsel emente/---Seitenwec hs el--- @ 3\mod_1221108045078_0.doc x @ 21810 @ @ 1
IEC 61131
[hex]
address
0x0000...0x00FF
%QW0...%QW255
0x0100...0x01FF
0x0200...0x02FF
%QW0...%QW255
0x0300...0x0FFF
0x1000...0x2FFF
%QW256...%QW1020 Physical output area (2)
%QW256...%QW1020 Physical output area (2)
Fieldbus Communication 169
Memory range
Physical output area (1)
First 256 Words of physical output data
-
MODBUS exception:
"Illegal data address"
Physical output area (1)
First 256 Words of physical output data
-
MODBUS exception:
"Illegal data address"
-
Configuration register (see Section
"Configuration Register")
-
MODBUS exception:
"Illegal data address"
Additional 764 Words physical output data
-
MODBUS exception:
"Illegal data address"
Additional 764 Words physical output data
-
MODBUS exception:
"Illegal data address"