Table 305: Description Of Marking Example For Approved Ex I I/O Module According To Atex And Iecex; Table 307: Description Of Marking Example For Approved Ex I I/O Module - WAGO -I/O-SYSTEM 750 XTR Manual

Fc ethernet g3 xtr fieldbus coupler ethernet; 3rd generation; extreme
Hide thumbs Also See for WAGO-I/O-SYSTEM 750 XTR:
Table of Contents

Advertisement

256 Use in Hazardous Environments
Table 305: Description of Marking Example for Approved Ex i I/O Module According to ATEX and
IECEx
Marking
TUEV 12 ATEX 106032 X
IECEx TUN 12 0039 X
Dust
II
3 (1) D
Ex
tc
[ia Da]
IIIC
T135°C
Dc
Mining
I
M2 (M1)
Ex
d
[ia Ma]
I
Mb
Gases
II
3 (1) G
Ex
ec
[ia Ga]
IIC
T4
Gc
Pos : 106.9 /Alle Serien (Allgemeine M odul e)/Übersc hriften/Ebene 3/Kennzeic hnung für die Vereinigten Staaten von Ameri ka (N EC) und Kanada (C EC) - Übersc hrift 3 @ 29\mod_1495099368853_21.doc x @ 422071 @ 3 @ 1
Manual
Version 1.3.0
750-352/040-000 FC ETHERNET G3 XTR
Description
Approving authority resp. certificate numbers
Equipment group: All except mining
Category 3 (Zone 22) equipment containing a safety
device for a category 1 (Zone 20) equipment
Explosion protection mark
Type of protection: Protection by enclosure
Type of protection and equipment protection level
(EPL): Associated apparatus with intrinsic safety
circuits for use in Zone 20
Explosion group of dust
Max. surface temperature of the enclosure
(without a dust layer)
Equipment protection level (EPL)
Equipment Group: Mining
Category: High level of protection with electrical
circuits which present a very high level of protection
Explosion protection mark
Type of protection: Flameproof enclosure
Type of protection and equipment protection level
(EPL): Associated apparatus with intrinsic safety
electrical circuits
Explosion group for electrical equipment for mines
susceptible to firedamp
Equipment protection level (EPL)
Equipment group: All except mining
Category 3 (Zone 2) equipment containing a safety
device for a category 1 (Zone 0) equipment
Explosion protection mark
Equipment protection by increased safety "e"
Type of protection and equipment protection level
(EPL): Associated apparatus with intrinsic safety
circuits for use in Zone 0
Explosion group of gas and vapours
Temperature class: Max. surface temperature
135 °C
Equipment protection level (EPL)
WAGO-I/O-SYSTEM 750 XTR

Advertisement

Table of Contents
loading

This manual is also suitable for:

750-352/040-000

Table of Contents