WAGO-I/O-SYSTEM 750 XTR
750-352/040-000 FC ETHERNET G3 XTR
Table 47: Blink Code Table for the 'I/O' LED Signaling, Error Code 1
Error code 1: "Hardware and configuration error"
Error
Argument
7
8
9
Pos : 73.10 /Serie 750 ( WAGO-I/O-SYST EM)/Diagnos e/F eldbus koppler/-c ontroll er/Bli nkc ode-Tabellen - F ehl erc ode 1 - 10...13 nicht genutzt (750- 352, 362, 852, 862) @ 8\mod_1280148304533_21.doc x @ 61301 @ @ 1
10 ... 13
Pos : 73.11 /Serie 750 ( WAGO-I/O-SYST EM)/Diagnos e/F eldbus koppler/-c ontroll er/Bli nkc ode-Tabellen - F ehl erc ode 1.14...5 ( 750-0352/040- 000) XTR @ 18\mod_1392138063428_21.doc x @ 145134 @ @ 1
14
Table 48: Blink Code Table for the 'I/O' LED Signaling, Error Code 2
Error code 2: -not used-
Error
Argument
-
Error Description
Solution
Invalid hardware-
1.
firmware
2.
combination.
1.
Timeout during serial
2.
EEPROM access.
1.
Bus controller
2.
initialization error
not used
Maximum number of
1.
gateway or mailbox
2.
modules exceeded
Error Description
Solution
Not used
Turn off the power supply for the node.
Replace the fieldbus coupler and turn the power supply on
again.
Turn off the power supply for the node.
Replace the fieldbus coupler and turn the power supply on
again.
Turn off the power supply for the node.
Replace the fieldbus coupler and turn the power supply on
again.
Turn off the power for the node.
Reduce the number of corresponding modules to a valid
number.
Diagnostics 133
Manual
Version 1.3.0