88
Commissioning

Figure 42: Address Selection Switch, for Example the Value Setting "50" (2

3.
Restart the fieldbus node after adjusting the address selection switch to
apply the configuration changes.
Pos : 67.18.1 /Serie 750 ( WAGO-I/O- SYST EM)/In Betri eb nehmen/F eldbus knoten in Betri eb nehmen/IP-Adres se mi t DHC P vergeben - Ü bersc hrift 3, Die Besc hr umfasst folg Arbeitssc hritte, Ü4 DHCP akti v @ 5\mod_1244201774491_21.doc x @ 35007 @ 3 @ 1
8.2.2

Assigning IP Address via DHCP

If you want to use DHCP to assign the IP address, it happens automatically via a
DHCP server on the network.
Pos : 67.18.2 /Serie 750 ( WAGO-I/O- SYST EM)/In Betri eb nehmen/F eldbus knoten in Betri eb nehmen/IP-Adres se mi t DHC P vergeben T eil 2 @ 9\mod_1282136848186_21.doc x @ 63897 @ 4 @ 1
Total network failure when there are two DHCP servers in the network!
To prevent network failure, never connect a PC, on which a DHCP server is
installed, to a global network. In larger networks, there is usually a DHCP server
already that can cause collisions and subsequent network failure.
There must be a DHCP server in the network for further configuration!
Install a DHCP server on your client PC in the local network if not already
available. You can download a DHCP server free of charge on the Internet.
Assign the DHCP server a fixed IP address and note common subnet!
Note that the DHCP server must have a fixed IP address and that the fieldbus
node and DHCP server must be in the same subnet.
Via DHCP assigned IP addresses are only temporarily valid!
Note that an IP address assigned via DHCP is limited in time. If the DHCP server
is not available at the end of its useful life, the fieldbus node sets the IP address
free and then the fieldbus node is no longer accessible!