WAGO-I/O-SYSTEM 750 XTR
750-352/040-000 FC ETHERNET G3 XTR
Assign the PC a fixed IP address and note common subnet!
Note that the PC, on which the BootP server is listed, must have a fixed IP
address and that the fieldbus node and PC must be in the same subnet.
6.
Note the IP address you have selected:
Fieldbus node IP address:
Pos : 67.22.18 /Seri e 750 ( WAGO-I/O-SYSTEM)/In Betrieb nehmen/Fel dbus knoten in Betrieb nehmen/IP- Adr ess e über BootP vergeben (Ü bersc hrift 4 und Schritte 1-3) @ 6\mod_1265023678369_21.doc x @ 49099 @ @ 1
1.
Based on the handling, which depends on the BootP program set, assign
the required IP address for your fieldbus node.
2.
Enable the query/response mechanism of the BootP protocol based on the
handling, which depends on the BootP program set or e. g. in "WAGO
Ethernet Settings" (Network tab, Source "BootP").
3.
To apply the new IP address, use e.g. a hardware reset to restart your
fieldbus node by interrupt the voltage supply for approx. 2 seconds.
4.
Restart the fieldbus node.
The fieldbus node then starts with the new IP address assigned via BootP.
5.
In order to use the IP address permanently, select in the WBM on "TCP/IP"
WBM page the option "IP configuration source: static" (see chapter "Apply
IP address permanently (option "static ")").
Pos : 67.22.19 /Seri e 750 ( WAGO-I/O-SYSTEM)/In Betrieb nehmen/Fel dbus knoten in Betrieb nehmen/IP- Adr ess e dauerhaft durc h Opti on „us e IP from EEPR OM" - Übersc hrift 4 @ 5\mod_1244025692102_21.doc x @ 34786 @ 4 @ 1
8.2.4.3
Assigning the IP address permanently by option "use IP from
EEPROM"
Pos : 67.22.20 /Seri e 750 ( WAGO-I/O-SYSTEM)/In Betrieb nehmen/Fel dbus knoten in Betrieb nehmen/Bei akti vi ertem BootP- Protokoll er wartet der Koppl er di e per manente Anwesenhei t (Koppl er) @ 6\mod_1264501767588_21.doc x @ 48743 @ @ 1
When the BootP protocol is enabled the coupler expects the BootP server to be
permanently available. If there is no BootP server available after a Power On
reset, the network will remain inactive.
Pos : 67.22.21 /Seri e 750 ( WAGO-I/O-SYSTEM)/In Betrieb nehmen/Fel dbus knoten in Betrieb nehmen/Hinweis: Für die dauer hafte Adress vergabe muss di e i m EEPROM g esp. ver wend. - BootP (Koppl er) @ 5\mod_1244028516394_21.doc x @ 34809 @ @ 1
IP stored in EEPROM must be used to assign the address permanently!
To apply the new IP address permanently in the fieldbus coupler, the option "use
IP from EEPROM" must be selected.
Thus, the IP address is automatically entered as static address and used in the
EEPROM.
Pos : 67.22.22 /Seri e 750 ( WAGO-I/O-SYSTEM)/In Betrieb nehmen/Fel dbus knoten in Betrieb nehmen/Das U msc halten auf die Option nehmen Si e i m Web- Bas ed-Manag. (-352, -881, -882) @ 9\mod_1292516140287_21.doc x @ 67573 @ @ 1
You can enable the option in the Web-based Management System.
Pos : 67.22.23 /D okumentation allgemein/Gliederungselemente/---Sei tenwechsel--- @ 3\mod_1221108045078_0.doc x @ 21810 @ @ 1
Commissioning
_ _ _ . _ _ _ . _ _ _ . _ _ _
95