10.1.1

Evaluating Fieldbus Status

The health of the ETHERNET Fieldbus is signaled through the top LED group
('LINK ACT 1, 2', 'MS', und 'NS').
Pos : 73.7.2 /Serie 750 (WAGO-I/O-SYST EM)/Diag nose/Fel dbus koppl er/-contr oller/F eldbusstatus aus wer ten ('LIN K ACT 1, 2', 'M S', 'NS') mit EtherN et/IP - MS und NS für EtherNet/IP @ 9\mod_1282558697263_21.doc x @ 64156 @ @ 1
The two-colored LEDs 'MS' (module status) and 'NS' (network status) are solely
used by the EtherNet/IP protocol. These two LEDs conform to the EtherNet/IP
specifications.
Pos : 73.7.3 /Serie 750 (WAGO-I/O-SYST EM)/Diag nose/Fel dbus koppl er/-contr oller/F eldbusstatus aus wer ten ('LIN K ACT 1, 2', 'M S, 'NS') - T abelle 'LIN K ACT 1, 2', 'MS' @ 9\mod_1282558855632_21.doc x @ 64159 @ @ 1
Table 45: Fieldbus Diagnostics – Solution in Event of Error
LED
Status
LINK ACT 1, 2
green
green
flashing
off
MS
green
green
flashing
red
red/green
flashing
off
NS
green
green
flashing
red
red
flashing
red/green
flashing
off
Pos : 73.8.1 /Serie 750 (WAGO-I/O-SYST EM)/Diag nose/Fel dbus koppl er/-contr oller/Knotenstatus aus werten 1 - I/O-LED ( alle Koppler/C ontroll er) @ 6\mod_1259229729546_21.doc x @ 45457 @ 3 @ 1
Meaning
The fieldbus node is connected to the
physical network.
The fieldbus node sends and receives
ETHERNET telegrams
The fieldbus node is not connected to
the physical network.
Normal operation
The system is not yet configures
The system indicates a not
remediable error
Self test
No system supply voltage
At least one connection (Modbus TCP
or EtherNet/IP) is developed (also
connection to the Message rout
applies)
No connection (Modbus TCP or
EtherNet/IP).
The system indicates a double IP-
address in the network
At least one connection (Modbus TCP
or EtherNet/IP) announced a Timeout,
where the controller functions as
target.
Self test
No IP address is assigned to the
system.
Diagnostics 129
Solution
-
-
1.
Check the fieldbus cable.
-
-
1.
Restart the device by turning the power
supply off and on again.
2.
If the error still exists, please contact
the I/O support.
-
1.
Check the supply voltage.
-
-
1.
Use an IP address that is not used yet.
1.
Restart the device by turning the power
supply off and on again.
2.
Develop a new connection.
-
1.
Assign to the system an IP address for
example by BootP or DHCP.