Data Exchange - WAGO -I/O-SYSTEM 750 XTR Manual

Fc ethernet g3 xtr fieldbus coupler ethernet; 3rd generation; extreme
Hide thumbs Also See for WAGO-I/O-SYSTEM 750 XTR:
Table of Contents

Advertisement

80
Function Description
Pos : 63 /All e Seri en (Allgemei ne Module)/Ü berschriften/Ebene 2/Datenaustausc h - Ü bers chrift 2 @ 4\mod_1241431718548_21.doc x @ 32202 @ 2 @ 1
7.3

Data Exchange

Pos : 64.1 /Serie 750 (WAGO-I/O-SYST EM)/F unktions beschr eibung/Datenaus tausc h/D atenaustaus ch - Ei nleitung (750- 341, -342, -352) (Koppler) @ 7\mod_1265975017174_21.doc x @ 50553 @ @ 1
With the fieldbus coupler, data is exchanged either via the MODBUS/TCP
protocol or via EtherNet/IP.
MODBUS/TCP works according to the master/slave principle. The master
controller can be a PC or a PLC.
The fieldbus couplers of the WAGO-I/O-SYSTEM 750 are slave devices.
The master requests communication. This request can be directed to certain
nodes by addressing. The nodes receive the request and, depending on the
request type, send a reply to the master.
Pos : 64.2 /Serie 750 (WAGO-I/O-SYST EM)/F unktions beschr eibung/Datenaus tausc h/D atenaustaus ch - Ei n F eldbus koppler kann ei ne bes timmte Anz ahl glei chz eitiger Verbindung en (Koppler) @ 7\mod_1265975390320_21.doc x @ 50556 @ @ 1
A defined number of simultaneous connections (socket connections) with other
network devices can be established to a fieldbus coupler:
Pos : 64.3 /Serie 750 (WAGO-I/O-SYST EM)/F unktions beschr eibung/Datenaus tausc h/D atenaustaus ch - Lis te gleichzeitiger Verbi ndungen (Soc ket-Verbi ndungen) (750- 352, -354) @ 7\mod_1265976319452_21.doc x @ 50569 @ @ 1
3 connections for HTTP (to read HTML pages from the coupler)
15 connections via MODBUS/TCP (to read or write input and output data of
the coupler)
128 connections for EtherNet/IP
10 connections for FTP
2 connections for SNMP
Pos : 64.4 /Serie 750 (WAGO-I/O-SYST EM)/F unktions beschr eibung/Datenaus tausc h/D atenaustaus ch - Sc hnitts tell en (Koppler) @ 7\mod_1265977486459_21.doc x @ 50572 @ @ 1
The maximum number of simultaneous connections can not be exceeded.
Existing connections must first be terminated before new ones can be set up.
The FC ETHERNET G3 XTR is essentially equipped with two interfaces for data
exchange:
the interface to the fieldbus (Master)
the interface to the I/O modules.
Data exchange takes place between the fieldbus master and the I/O modules.
Pos : 64.5 /Serie 750 (WAGO-I/O-SYST EM)/F unktions beschr eibung/Datenaus tausc h/D atenaustaus ch - Wird als F eldbus MODBU S genutzt, greift der M aster über die ( Koppler) @ 7\mod_1265978034343_21.doc x @ 50575 @ @ 1
If MODBUS is used as the fieldbus, the MODBUS master accesses the date
using the MODBUS functions implemented in the fieldbus coupler; EtherNet/IP,
in contrast, uses an object model for data access.
Pos : 64.6 /Serie 750 (WAGO-I/O-SYST EM)/F unktions beschr eibung/Datenaus tausc h/Speic her ber eiche M ODBU S/Speic her ber eiche M ODBU S - Bild ( Koppler) ( 750-306, -341, 342, 352, 354) @ 7\mod_1265978270612_21.doc x @ 50588 @ @ 1
Manual
Version 1.3.0
WAGO-I/O-SYSTEM 750 XTR
750-352/040-000 FC ETHERNET G3 XTR