Overall Configuration - WAGO -I/O-SYSTEM 750 XTR Manual

Fc ethernet g3 xtr fieldbus coupler ethernet; 3rd generation; extreme
Hide thumbs Also See for WAGO-I/O-SYSTEM 750 XTR:
Table of Contents

Advertisement

WAGO-I/O-SYSTEM 750 XTR
750-352/040-000 FC ETHERNET G3 XTR
For vibration loads > 4g, observe the following installation instructions:
Use pan-head screws or blind rivets at least every 60 mm (12 mm pin
spacing) to secure the DIN rail.
Make the open conductor length between strain relief and wire connection
as short as possible.
Use the reinforced end stop 249-197.
Pos : 51.3 /Serie 750 (WAGO-I/O-SYST EM)/M ontieren/D emontieren/Gesamtaus bau XTR @ 16\mod_1373976975062_21.doc x @ 126295 @ 2 @ 1
5.2

Overall Configuration

The maximum total length of a fieldbus node without fieldbus coupler/controller is
780 mm including end module. The width of the end module is 12 mm. When
assembled, the I/O modules have a maximum length of 768 mm.
Examples:
64 I/O modules with a 12 mm width can be connected to a fieldbus
coupler/controller.
32 I/O modules with a 24 mm width can be connected to a fieldbus
coupler/controller.
Exception:
The number of connected I/O modules also depends on the type of fieldbus
coupler/controller is used. For example, the maximum number of stackable I/O
modules on one PROFIBUS DP/V1 fieldbus coupler/controller is 63 with no
passive I/O modules and end module.
Observe maximum total length of a fieldbus node!
The maximum total length of a fieldbus node without fieldbus coupler/controller
may not exceed 780 mm.
Also note the limitations of individual fieldbus couplers/controllers.
Pos : 51.4 /Dokumentation allgemei n/Glieder ungs elemente/---Seitenwechs el--- @ 3\mod_1221108045078_0.doc x @ 21810 @ @ 1
Mounting
67
Manual
Version 1.3.0

Advertisement

Table of Contents
loading

This manual is also suitable for:

750-352/040-000

Table of Contents