Table 52: Blink Code- Table For The I/O Led Signaling, Error Code 6 - WAGO -I/O-SYSTEM 750 XTR Manual

Fc ethernet g3 xtr fieldbus coupler ethernet; 3rd generation; extreme
Hide thumbs Also See for WAGO-I/O-SYSTEM 750 XTR:
Table of Contents

Advertisement

136 Diagnostics

Table 52: Blink code- table for the I/O LED signaling, error code 6

Error code 6: "Fieldbus specific errors"
Error
Argument
1
2
3
4
5
6
7
8
9
Manual
Version 1.3.0
Error description
Solution
1.
Invalid MACID
2.
3.
1.
Ethernet Hardware
initialization error
2.
1.
TCP/IP initialization
error
2.
Network configuration
1.
error (no IP Address)
1.
Application protocol
initialization error
2.
Process image is too
1.
large
2.
1.
Double IP address in
network
2.
1.
2.
Error when building the
3.
process image
4.
Error with mapping
between bus modules
1.
and fieldbus
WAGO-I/O-SYSTEM 750 XTR
750-352/040-000 FC ETHERNET G3 XTR
Turn off the power supply of the node.
Exchange fieldbus coupler.
Turn the power supply on again.
Restart the fieldbus coupler by turning the power supply
off and on again.
If the error still exists, exchange the fieldbus coupler.
Restart the fieldbus coupler by turning the power supply
off and on again.
If the error still exists, exchange the bus coupler.
Check the settings of BootP server.
Restart the fieldbus coupler by turning the power supply
off and on again.
If the error still exists, exchange the bus coupler.
Turn off the power supply of the node.
Reduce number of I/O modules
Change configuration. Use another IP address, which is
not yet present in network.
Restart the fieldbus coupler by turning the power supply
off and on again.
Turn off the power supply of the node.
Reduce number of I/O modules
Restart the fieldbus coupler by turning the power supply
off and on again.
If the error still exists, exchange the bus coupler.
Check io-config.xml file on the fieldbus coupler

Advertisement

Table of Contents
loading

This manual is also suitable for:

750-352/040-000

Table of Contents