WAGO-I/O-SYSTEM 750 XTR
750-352/040-000 FC ETHERNET G3 XTR
The following steps are included:

Note MAC ID

Note IP address
Assigning the IP address and enable BootP
Assigning the IP address permanently by option "use IP from EEPROM"
Pos : 67.22.7 /Serie 750 ( WAGO-I/O- SYST EM)/In Betri eb nehmen/F eldbus knoten in Betri eb nehmen/MAC- ID ermittel n ( BootP) Übersc hrift 4 @ 6\mod_1264500781687_21.doc x @ 48740 @ 4 @ 1
8.2.4.1
Note MAC ID
Pos : 67.22.8 /Serie 750 ( WAGO-I/O- SYST EM)/In Betri eb nehmen/F eldbus knoten in Betri eb nehmen/MAC- ID ermittel n - Sc hritte 1- 2 ( Koppl er) @ 5\mod_1244023441128_21.doc x @ 34776 @ @ 1
1.
Write down the coupler's MAC address (see label or peel-off strip).
If the fieldbus is already installed, turn off the operating voltage of the
fieldbus coupler, then take the fieldbus coupler out of the assembly of your
fieldbus node and note the MAC ID of your fieldbus coupler.
The MAC ID is applied to the back of the fieldbus coupler or on the self-
adhesive peel-off strip on the side of the fieldbus coupler.
MAC ID of the fieldbus coupler:
2.
Plug the fieldbus coupler into the assembly of the fieldbus node.
Pos : 67.22.9 /Serie 750 ( WAGO-I/O- SYST EM)/In Betri eb nehmen/F eldbus knoten in Betri eb nehmen/PC und F eldbus knoten an Fel dbus ansc hluss ansc hließ en (Aufz ählung For tsetzung) @ 4\mod_1243520482117_21.doc x @ 34109 @ @ 1
3.
Use the fieldbus cable to connect the fieldbus connection of your
mechanically and electrically assembled fieldbus node to an open interface
on your PC.
The PC must be equipped with a network card for this connection. The
transfer rate then depends on the network card of your PC.
Pos : 67.22.10 /Seri e 750 ( WAGO-I/O-SYSTEM)/In Betrieb nehmen/Fel dbus knoten in Betrieb nehmen/Starten Si e den PC, der die F unkti on des M asters und BootP- Ser vers überni mmt. @ 4\mod_1239087816984_21.doc x @ 30067 @ @ 1
4.
Start the PC that assumes the function of the master and BootP server.
Pos : 67.22.11 /Seri e 750 ( WAGO-I/O-SYSTEM)/In Betrieb nehmen/Fel dbus knoten in Betrieb nehmen/Sc halten Sie di e Spannungsvers orgung am Koppler (DC-24V-Netzteil) ein. @ 6\mod_1264489453689_21.doc x @ 48671 @ @ 1
5.
Switch on the power at the fieldbus coupler (DC 24 V power supply unit).
Pos : 67.22.12 /Seri e 750 ( WAGO-I/O-SYSTEM)/In Betrieb nehmen/Fel dbus knoten in Betrieb nehmen/Hoc hl auf und LEDs (Koppler) @ 4\mod_1243590574487_21.doc x @ 34500 @ @ 1
The fieldbus coupler is initialized. The coupler determines the I/O module
configuration and creates a process image.
During start-up, the I/O LED (red) flashes.
If the I/O LED lights up green after a brief period, the fieldbus coupler is
operational.
Pos : 67.22.13 /Seri e 750 ( WAGO-I/O-SYSTEM)/In Betrieb nehmen/Fel dbus knoten in Betrieb nehmen/Hoc hl auf und LEDs - F ehl er allgemein, Hi nweis : Sig nalisi erung/Blinkcode-Aus w. @ 4\mod_1243594306433_21.doc x @ 34538 @ @ 1
If an error occurs during start-up indicated by the I/O LED flashing red, evaluate
the error code and argument and resolve the error.
More information about LED signaling
The exact description for evaluating the LED signal displayed is available in the
section "Diagnostics" > ... > "LED Signaling".
Pos : 67.22.14 /Seri e 750 ( WAGO-I/O-SYSTEM)/In Betrieb nehmen/Fel dbus knoten in Betrieb nehmen/Hoc hl auf und LEDs - F ehl er: keine IP ( Koppler) @ 6\mod_1264498475545_21.doc x @ 48707 @ @ 1
Error code 6, followed by error argument 4, is indicated by the I/O LED after
coupler start-up with 6 red error code flashes, followed by four red flashes of the
error argument. This indicates that an IP address has not yet been assigned.
Pos : 67.22.15 /D okumentation allgemein/Gliederungselemente/---Sei tenwechsel--- @ 3\mod_1221108045078_0.doc x @ 21810 @ @ 1
0 0 : 3 0 : D E : _ _ : _ _ : _ _
Commissioning