WAGO -I/O-SYSTEM 750 XTR Manual page 29

Fc ethernet g3 xtr fieldbus coupler ethernet; 3rd generation; extreme
Hide thumbs Also See for WAGO-I/O-SYSTEM 750 XTR:
Table of Contents

Advertisement

WAGO-I/O-SYSTEM 750 XTR
750-352/040-000 FC ETHERNET G3 XTR
Fieldbus coupler or controller
Internal system supply module
Input current I
Pos : 19.16.25 /Seri e 750 ( WAGO-I/O-SYSTEM)/Systembes chr eibung/Versorgung/Systemvers orgung - Ausl egung - n=N etzteil wir kungsgrad bei N ennlast 24 V (allgemein) @ 8\mod_1279035664863_21.doc x @ 59866 @ @ 1
Pos : 19.16.26 /Seri e 750 ( WAGO-I/O-SYSTEM)/Systembes chr eibung/Versorgung/Systemvers orgung - Ausl egung - Hi nweis: Bei Test der Str omaufnahme Ausg äng e akti vi eren @ 3\mod_1232950110750_21.doc x @ 26812 @ @ 1
Activate all outputs when testing the current consumption!
If the electrical consumption of a power supply point for the 24 V system
supply exceeds 500 mA, then the cause may be an improperly
dimensioned node or a defect.
During the test, you must activate all outputs.
Pos : 19.16.27 /Seri e 750 ( WAGO-I/O-SYSTEM)/Systembes chr eibung/Versorgung/F eldversorgung - Ü bersc hrift 3 @ 3\mod_1232950080953_21.doc x @ 26688 @ 3 @ 1
I
= Sum of all the internal current consumption of the connected
(5 V) total
bus modules + internal current consumption fieldbus
coupler/controller
I
= Sum of all the internal current consumption of the connected
(5 V) total
bus modules at internal system supply module
5 V
=
*
(24 V)
24 V
η = Efficiency of the power supply at nominal load 24 V
System Description
I
(5 V) total
η
29
Manual
Version 1.3.0

Advertisement

Table of Contents
loading

This manual is also suitable for:

750-352/040-000

Table of Contents