200 Fieldbus Communication
Common Service
Table 186: Static assembly instances – Common service
Service code Service
0E
hex
10
hex
Pos : 96.6 /Serie 750 (WAGO-I/O-SYST EM)/F unktions beschr eibung/Fel dbus kommuni kati on/EtherNetIP/Common Ser vic es (ohne Diagnos e) @ 8\mod_1276170797909_21.doc x @ 57633 @ @ 1
The software inspects the writing of attribute 3 of assembly instances 101, 102
and 103. If the limit value has been exceeded, it is identified and, if necessary,
corrected. However, a write request is not rejected. This means that if less data is
received than expected, only this data is written. If more data is received than
expected, the received data at the upper limit is deleted. In the case of explicit
messages, however, a defined CIP is generated even though the data has been
written.
Pos : 96.7 /Serie 750 (WAGO-I/O-SYST EM)/F unktions beschr eibung/Fel dbus kommuni kati on/EtherNetIP/Connec tion Obj ect ( 05hex), C onnecti on Manager Obj ect ( 06hex) @ 8\mod_1276182355206_21.doc x @ 57650 @ 44 @ 1
11.3.5.7

Connection (05

Because the connections are established and terminated via the connection
manager, the class and instance attributes of this class are not visible.
11.3.5.8

Connection Manager (06

The "Connection Manager Object" provides the internal resources that are
required for the input and output data and explicit messages. In addition, the
administration of this resource is an assignment of the "Connection Manager
Object".
For each connection (input and output data or explicit), another instance of the
connection class is created. The connection parameters are extracted from the
"Forward Open" service, which is responsible for establishing a connection.
The following services are supported for the first instance:
Forward_Open
Unconnected_Send
Forward_Close
No class and instance attributes are visible.
Pos : 96.8 /Serie 750 (WAGO-I/O-SYST EM)/F unktions beschr eibung/Fel dbus kommuni kati on/EtherNetIP/Port Cl ass, TCP IP Interface, Ethernet Li nk ( 3 Port) @ 3\mod_1233753561578_21.doc x @ 27067 @ 444 @ 1
11.3.5.9
Port Class (F4
The "Port Class Object" specifies the existing CIP ports on the fieldbus
coupler/coupler. There is one instance for each CIP port.
Manual
Version 1.3.0
Service name
available
Class
Instance
Yes
Yes
Get_Attribute_Single Supplies contents of the appropriate attribute
No
Yes
Set_Attribute_Single
)
hex
)
hex
)
hex
WAGO-I/O-SYSTEM 750 XTR
750-352/040-000 FC ETHERNET G3 XTR
Description
Modifies an attribute value