Figure 53: Node Status – I/O LED Signaling

Figure 54: Error Message Coding

Example of a module error:
The I/O LED starts the error display with the first flashing sequence
(approx. 10 Hz).
After the first break, the second flashing sequence starts (approx. 1 Hz):
The I/O LED blinks four times.
Error code 4 indicates "data error internal data bus".
After the second break, the third flashing sequence starts (approx. 1 Hz):
The I/O LED blinks twelve times.
Diagnostics 131