Table 118: Register Address 0x1006

Register address 0x1006 (4102
Value
Access
Standard
Description

Table 119: Register Address 0x1007

Register address 0x1007 (4103
Value
Access
Standard
Description

Table 120: Register Address 0x1008

Register address 0x1008 (4104
Value
Access
Standard
Description

Table 121: Register Address 0x1009

Register address 0x1009 (4105
Value
Access
Standard
Description

Table 122: Register Address 0x100A

Register address 0x100A (4106
Value
Access
Standard
Description
Pos : 94.34 /Serie 750 ( WAGO-I/O-SYST EM)/Funkti onsbesc hrei bung/F eldbus kommuni kation/M ODBU S/Z ugriff auf R egister werte - Watchdog (Beispi el Z eitüberschr eitung) @ 4\mod_1235634365875_21.doc x @ 27793 @ @ 1
The length of each register is 1 word; i.e., with each access only one word can be
written or read. Following are two examples of how to set the value for a time
overrun:
)
dez
While watchdog is running, WD_RUNNING
Read
0x0000
Current watchdog status.
at 0x0000: Watchdog not active
at 0x0001: Watchdog active
at 0x0002: Watchdog exhausted.
)
dez
Restart watchdog, WD_RESTART
Read/write
0x0000
This register restarts the watchdog timer after time out by writing a value of 0x1
into it. If the watchdog was stopped before the time out, it is not restarted.
)
dez
Simply stop watchdog, WD_AC_STOP_SIMPLE
Read/write
0x0000
This register stops the watchdog by writing the value 0xAA55 or 0x55AA into it.
The watchdog timeout fault is deactivated and it is possible to write in the
watchdog register again. If there is an existing watchdog fault, it is reset
)
dez
Close Modbus socket after watchdog timeout
Read/write
0x0000
0: Modbus socket is not closed
1: Modbus socket is closed
)
dez
Watchdog type Standard/Alternative
Read/write
0x0000
0: Modbus watchdog type "Standard"
1: Modbus watchdog type "Alternative"
Fieldbus Communication 175