Modbus Register Mapping; Table 106: Register Access Reading (With Fc3 And Fc4) - WAGO -I/O-SYSTEM 750 XTR Manual

Fc ethernet g3 xtr fieldbus coupler ethernet; 3rd generation; extreme
Hide thumbs Also See for WAGO-I/O-SYSTEM 750 XTR:
Table of Contents

Advertisement

168 Fieldbus Communication
Note that if the register ranges overlap, the results are undefined!
If register areas for read and write overlap, the results are undefined.
Pos : 94.17 /D okumentati on allgemei n/Gli ederungsel emente/---Seitenwec hs el--- @ 3\mod_1221108045078_0.doc x @ 21810 @ @ 1
Pos : 94.18 /Serie 750 ( WAGO-I/O-SYST EM)/Funkti onsbesc hrei bung/F eldbus kommuni kation/M ODBU S/MOD BU S-Register-Mappi ng - Ei nleitung (352) ( Koppler) @ 8\mod_1280224404469_21.doc x @ 61350 @ 3 @ 1
11.2.4

MODBUS Register Mapping

The following tables display the MODBUS addressing and the internal variables.
Via the register services the states of the complex and digital I/O modules can be
determined or changed.
Pos : 94.19 /Serie 750 ( WAGO-I/O-SYST EM)/Funkti onsbesc hrei bung/F eldbus kommuni kation/M ODBU S/MOD BU S-Register-Mappi ng - Registerzugriff Les en (mi t FC 3 und FC 4) (-352) @ 8\mod_1280154005904_21.doc x @ 61304 @ @ 1
Register Access Reading (with FC3 and FC4)

Table 106: Register Access Reading (with FC3 and FC4)

MODBUS address
[dec]
0...255
256...511
512...767
768...4095
4096...12287
12288...24575 0x3000...0x5FFF
24576...25339 0x6000...0x62FB
25340...28671 0x62FC...0x6FFF
28672...29435 0x7000...0x72FB
29436...65535 0x72FC...0xFFFF
Pos : 94.20 /Serie 750 ( WAGO-I/O-SYST EM)/Funkti onsbesc hrei bung/F eldbus kommuni kation/M ODBU S/MOD BU S-Register-Mappi ng - Registerzugriff Sc hrei ben ( mit FC6 und FC 16) (- 352) @ 8\mod_1280154884157_21.doc x @ 61307 @ @ 1
Manual
Version 1.3.0
IEC 61131
[hex]
address
0x0000...0x00FF
%IW0...%IW255
0x0100...0x01FF
0x0200...0x02FF
%QW0...%QW255
0x0300...0x0FFF
0x1000...0x2FFF
%IW256...%IW1020
%QW256...%QW1020 Physical output area (2)
WAGO-I/O-SYSTEM 750 XTR
750-352/040-000 FC ETHERNET G3 XTR
Memory range
Physical input area (1)
First 256 Words of physical input data
-
MODBUS exception:
"Illegal data address"
Physical output area (1)
First 256 Words of physical output data
-
MODBUS exception:
"Illegal data address"
-
Configuration register (see Section
„Configuration Register")
-
MODBUS exception:
"Illegal data address"
Physical input area (2)
Additional 764 Words physical input data
-
MODBUS exception:
"Illegal data address"
Additional 764 Words physical output data
-
MODBUS exception:
"Illegal data address"