Page 1
Manual WAGO I/O System 750 XTR 750-1417/040-000 8DI 24 VDC 3ms LSS 2-wire XTR 8-Channel Digital Input; 24 VDC; 3 ms; Low-Side Switching; 2-Wire Connection; Extreme Version 1.0.0...
Page 2
We wish to point out that the software and hardware terms as well as the trademarks of companies used and/or mentioned in the present manual are generally protected by trademark or patent. WAGO is a registered trademark of WAGO Verwaltungsgesellschaft mbH. Manual Version 1.0.0...
WAGO I/O System 750 XTR Table of Contents 750-1417/040-000 8DI 24 VDC 3ms LSS 2-wire XTR Table of Contents Notes about this Documentation ............. 5 Validity of this Documentation..............5 Copyright ....................5 Symbols ....................6 Number Notation ..................8 Font Conventions ...................
Page 4
Table of Contents WAGO I/O System 750 XTR 750-1417/040-000 8DI 24 VDC 3ms LSS 2-wire XTR Use in Hazardous Environments ............44 Marking Configuration Examples ............45 7.1.1 Marking for Europe According to ATEX and IECEx ......45 7.1.2 Marking for the United States of America (NEC) and Canada (CEC) ....................
(8DI 24 VDC 3ms LSS 2-wire XTR). The I/O module 750-1417/040-000 shall only be installed and operated according to the instructions in this manual, in the system description for the WAGO I/O System 750 XTR and in the manual for the used fieldbus coupler/controller.
Notes about this Documentation WAGO I/O System 750 XTR 750-1417/040-000 8DI 24 VDC 3ms LSS 2-wire XTR Symbols Personal Injury! Indicates a high-risk, imminently hazardous situation which, if not avoided, will result in death or serious injury. Personal Injury Caused by Electric Current! Indicates a high-risk, imminently hazardous situation which, if not avoided, will result in death or serious injury.
Page 7
WAGO I/O System 750 XTR Notes about this Documentation 750-1417/040-000 8DI 24 VDC 3ms LSS 2-wire XTR Additional Information: Refers to additional information which is not an integral part of this documentation (e.g., the Internet). Manual Version 1.0.0...
Notes about this Documentation WAGO I/O System 750 XTR 750-1417/040-000 8DI 24 VDC 3ms LSS 2-wire XTR Number Notation Table 1: Number Notation Number Code Example Note Decimal Normal notation Hexadecimal 0x64 C notation Binary '100' In quotation marks, nibble separated '0110.0100'...
2.1.1 Subject to Changes WAGO GmbH & Co. KG reserves the right to provide for any alterations or modifications. WAGO GmbH & Co. KG owns all rights arising from the granting of patents or from the legal protection of utility patents. Third-party products are always mentioned without any reference to patent rights.
These modules contain no parts that can be serviced or repaired by the user. The following actions will result in the exclusion of liability on the part of WAGO GmbH & Co. KG: •...
WAGO I/O System 750 XTR Important Notes 750-1417/040-000 8DI 24 VDC 3ms LSS 2-wire XTR Environmentally friendly disposal benefits health and protects the environment from harmful substances in electrical and electronic equipment. • Observe national and local regulations for the disposal of electrical and electronic equipment.
Important Notes WAGO I/O System 750 XTR 750-1417/040-000 8DI 24 VDC 3ms LSS 2-wire XTR Safety Advice (Precautions) For installing and operating purposes of the relevant device to your system the following safety precautions shall be observed: Do not work on devices while energized! All power sources to the device shall be switched off prior to performing any installation, repair or maintenance work.
Page 13
WAGO I/O System 750 XTR Important Notes 750-1417/040-000 8DI 24 VDC 3ms LSS 2-wire XTR Power from SELV/PELV power supply only! All field signals and field supplies connected to this XTR I/O module (750-1417/040-000) must be powered from SELV/PELV power supply(s)!
Page 14
Important Notes WAGO I/O System 750 XTR 750-1417/040-000 8DI 24 VDC 3ms LSS 2-wire XTR Do not exceed the maximum total current for I/O modules (5 VDC) via data contacts! The maximum permissible total current for internal system supply of the I/O modules may not be exceeded.
Page 15
WAGO I/O System 750 XTR Important Notes 750-1417/040-000 8DI 24 VDC 3ms LSS 2-wire XTR Do not reverse the polarity of connection lines! Avoid reverse polarity of data and power supply lines, as this may damage the devices involved. Avoid electrostatic discharge! The devices are equipped with electronic components that may be destroyed by electrostatic discharge when touched.
Device Description WAGO I/O System 750 XTR 750-1417/040-000 8DI 24 VDC 3ms LSS 2-wire XTR Device Description The digital input module 750-1417/040-000 (8DI 24 VDC 3ms LSS 2-wire XTR) receives control signals from digital field (e.g. of sensors, transmitters, switches or proximity switches).
Page 17
WAGO I/O System 750 XTR Device Description 750-1417/040-000 8DI 24 VDC 3ms LSS 2-wire XTR Use supply modules for ground (earth)! The I/O module has no power jumper contacts for receiving and transmitting the earth potential. Use a supply module when an earth potential is needed for the subsequent I/O modules.
WAGO I/O System 750 XTR Device Description 750-1417/040-000 8DI 24 VDC 3ms LSS 2-wire XTR Connectors 3.2.1 Data Contacts/Local Bus Communication between the fieldbus coupler/controller and the I/O modules as well as the system supply of the I/O modules is carried out via the local bus. The contacting for the local bus consists of 6 data contacts, which are available as self-cleaning gold spring contacts.
Device Description WAGO I/O System 750 XTR 750-1417/040-000 8DI 24 VDC 3ms LSS 2-wire XTR 3.2.2 Power Jumper Contacts/Field Supply Power from SELV/PELV power supply only! All field signals and field supplies connected to this XTR I/O module (750-1417/040-000) must be powered from SELV/PELV power supply(s)! Risk of injury due to sharp-edged blade contacts! The blade contacts are sharp-edged.
Page 21
WAGO I/O System 750 XTR Device Description 750-1417/040-000 8DI 24 VDC 3ms LSS 2-wire XTR Do not exceed maximum values via power contacts! The maximum current that can flow through the power jumper contacts is 10 A. The power jumper contacts can be damaged and the permissible operating temperature can be exceeded by higher current values.
WAGO I/O System 750 XTR Device Description 750-1417/040-000 8DI 24 VDC 3ms LSS 2-wire XTR Display Elements Figure 5: Display Elements Table 6: Legend for Figure “Display Elements” Channel Designation State Function Input DI 1: Signal voltage (0) State DI 1...
WAGO I/O System 750 XTR Device Description 750-1417/040-000 8DI 24 VDC 3ms LSS 2-wire XTR Technical Data 3.6.1 Device Data Table 7: Technical Data – Device Width 12 mm Height 100 mm Depth 69 mm Weight 45.3 g Number of digital inputs...
Device Description WAGO I/O System 750 XTR 750-1417/040-000 8DI 24 VDC 3ms LSS 2-wire XTR Approvals For current approvals, please go to: www.wago.com/<Item number>. The following approvals have been granted to 750-1417/040-000 I/O modules: Conformity Marking UL E175199 for use in Ordinary...
Page 29
WAGO I/O System 750 XTR Device Description 750-1417/040-000 8DI 24 VDC 3ms LSS 2-wire XTR The following ship approvals are pending for 750-1417/040-000 I/O modules: ABS (American Bureau of Shipping) LR (Lloyd’s Register) Env. 1, 2, 3, 4 For more information about the ship approvals: Note the “Supplementary Power Supply Regulations”...
WAGO I/O System 750 XTR Device Description 750-1417/040-000 8DI 24 VDC 3ms LSS 2-wire XTR Table 15: Climatic and Mechanical Environmental Conditions and Shipbuilding Standard Test Value Transport EN 60870-2-2 Ct2(2k4) (except precipitation/water/moisture) Mechanical Environmental Conditions EN 61850-3 Achieved EN 60870-2-2...
Device Description WAGO I/O System 750 XTR 750-1417/040-000 8DI 24 VDC 3ms LSS 2-wire XTR The I/O module 750-1417/040-000 meets the following EMC standards as these standards relate to the I/O module: Table 16: EMC – Product- and Generic Standards...
MTBF values (acc. to MIL-HDBK-217-F2) are available and can be provided on request for specific projects WAGO is a company certified in accordance with the IRIS quality standard. Table 20: Further EMC Requirements for Railroad Applications Requirement Fulfills Class EBA Regulation No. EMC 06...
Process Image WAGO I/O System 750 XTR 750-1417/040-000 8DI 24 VDC 3ms LSS 2-wire XTR Process Image Table 21: Input Bits Bit 7 Bit 6 Bit 5 Bit 4 Bit 3 Bit 2 Bit 1 Bit 0 DI 8 DI 7...
750-1417/040-000 8DI 24 VDC 3ms LSS 2-wire XTR Mounting Mounting Sequence Fieldbus couplers, controllers and I/O modules of the WAGO I/O System 750 are snapped directly on a carrier rail in accordance with the European standard EN 60175 (DIN 35).
Mounting WAGO I/O System 750 XTR 750-1417/040-000 8DI 24 VDC 3ms LSS 2-wire XTR Inserting and Removing Devices Do not touch hot surfaces! The surface of the housing can become hot during operation. If the device was operated at high ambient temperatures, allow it to cool off before touching it.
WAGO I/O System 750 XTR Mounting 750-1417/040-000 8DI 24 VDC 3ms LSS 2-wire XTR Figure 8: Snap the I/O Module into Place (Example) Check that the I/O module is seated securely on the carrier rail and in the assembly. The I/O module must not be inserted crooked or askew.
Do not connect more than one conductor at one single connection! If more than one conductor must be routed to one connection, these must be connected in an up-circuit wiring assembly, for example using WAGO feed- through terminals. Terminate both solid and stranded or ferruled conductors by simply pushing them in - no tool required.
WAGO I/O System 750 XTR Connect Devices 750-1417/040-000 8DI 24 VDC 3ms LSS 2-wire XTR Connection Example Figure 11: Connection Example with 2 Switches on Channel 1 and 2 Manual Version 1.0.0...
750-1417/040-000 8DI 24 VDC 3ms LSS 2-wire XTR Use in Hazardous Environments The WAGO I/O System 750 (electrical equipment) is designed for use in Zone 2 hazardous areas and shall be used in accordance with the marking and installation regulations.
WAGO I/O System 750 XTR Use in Hazardous Environments 750-1417/040-000 8DI 24 VDC 3ms LSS 2-wire XTR Marking Configuration Examples 7.1.1 Marking for Europe According to ATEX and IECEx Figure 12: Marking Example per ATEX and IECEx Figure 13: Text Detail – Marking Example per ATEX and IECEx Manual Version 1.0.0...
Use in Hazardous Environments WAGO I/O System 750 XTR 750-1417/040-000 8DI 24 VDC 3ms LSS 2-wire XTR Table 22: Description of the Marking Example per ATEX and IECEx Marking Text Description TUEV 07 ATEX 554086 X Approving authority or certificate numbers IECEx TUN 09.0001 X...
WAGO I/O System 750 XTR Use in Hazardous Environments 750-1417/040-000 8DI 24 VDC 3ms LSS 2-wire XTR Figure 14: Marking Example of an Approved I/O Module Ex i per ATEX and IECEx Figure 15: Text Detail – Marking Example of an Approved I/O Module Ex i...
Use in Hazardous Environments WAGO I/O System 750 XTR 750-1417/040-000 8DI 24 VDC 3ms LSS 2-wire XTR Table 23: Description of the Marking Example of an Approved I/O Module Ex i per ATEX and IECEx Marking Text Description TUEV 12 ATEX 106032 X...
WAGO I/O System 750 XTR Use in Hazardous Environments 750-1417/040-000 8DI 24 VDC 3ms LSS 2-wire XTR 7.1.2 Marking for the United States of America (NEC) and Canada (CEC) Figure 16: Marking Example According to NEC Figure 17: Text Detail – Marking Example According to NEC 500...
Use in Hazardous Environments WAGO I/O System 750 XTR 750-1417/040-000 8DI 24 VDC 3ms LSS 2-wire XTR Figure 18: Text Detail – Marking Example for Approved I/O Module Ex i According to NEC 505 Table 25: Description of Marking Example for Approved I/O Module Ex i According to NEC 505...
WAGO I/O System 750 XTR Use in Hazardous Environments 750-1417/040-000 8DI 24 VDC 3ms LSS 2-wire XTR Figure 20: Text Detail – Marking Example for Approved I/O Module Ex i According to CEC 18 attachment J Table 27: Description of Marking Example for Approved I/O Module Ex i According to CEC 18...
Use in Hazardous Environments WAGO I/O System 750 XTR 750-1417/040-000 8DI 24 VDC 3ms LSS 2-wire XTR Installation Regulations For the installation and operation of electrical equipment in hazardous areas, the valid national and international rules and regulations which are applicable at the installation location must be carefully followed.
Page 53
WAGO I/O System 750 XTR Use in Hazardous Environments 750-1417/040-000 8DI 24 VDC 3ms LSS 2-wire XTR Explosive atmosphere occurring simultaneously with assembly, installation or repair work must be ruled out. Among other things, these include the following activities •...
Use in Hazardous Environments WAGO I/O System 750 XTR 750-1417/040-000 8DI 24 VDC 3ms LSS 2-wire XTR 7.2.2 Special Notes Regarding UL Hazardous Location For UL Hazardous Location acc. to UL File E198726, the following additional requirements apply: • Use in Class I, Division 2, Group A, B, C, D or non-hazardous areas only •...
Need help?
Do you have a question about the 750 XTR and is the answer not in the manual?
Questions and answers