2.1.1.8.1 Message codes for the extended control byte ......18 2.1.1.8.2 Message codes for the extended status byte......19 2.1.1.8.3 Use of the module 750-643 with programmable fieldbus controllers................. 20 2.1.1.8.3.1 Compatibility............... 21 2.1.1.8.3.2 Overview of function blocks ..........21 2.1.1.8.4...
Co. KG, Minden, Germany. Non-observance will involve the right to assert damage claims. WAGO Kontakttechnik GmbH & Co. KG reserves the right to provide for any alterations or modifications that serve to increase the efficiency of technical progress. WAGO Kontakttechnik GmbH & Co. KG owns all rights arising from the granting of patents or from the legal protection of utility patents.
Legal Bases All responsible persons have to familiarize themselves with the underlying legal standards to be applied. WAGO Kontakttechnik GmbH & Co. KG does not assume any liability whatsoever resulting from improper handling and damage incurred to both WAGO´s own and third-party products by disregarding detailed information in this Manual.
(emissions of interference) in compliance with EN 61000-6-3. You will find the detailed information in section "WAGO-I/O-SYSTEM 750" "System Description" "Technical Data". Please observe the safety precautions against electrostatic discharge in accordance with DIN EN 61340-5-1/-3.
Observe the precautionary measure for handling components at risk of electrostatic discharge. Note Make important notes that are to be complied with so that a trouble-free and efficient device operation can be guaranteed. Additional Information References to additional literature, manuals, data sheets and internet pages. WAGO-I/O-SYSTEM 750 I/O Modules...
Danger The WAGO-I/O-SYSTEM 750 and its components are an open system. It must only be assembled in housings, cabinets or in electrical operation rooms. Access is only permitted via a key or tool to authorized qualified personnel.
'0110.0100' nibble separated with dots (.) 1.7 Scope This manual describes the Special Module 750-643 MP-Bus Master Module of the modular WAGO-I/O-SYSTEM 750. Handling, assembly and start-up are described in the manual of the Fieldbus Coupler. Therefore this documentation is valid only in the connection with the appropriate manual.
The I/O module 750-643 module acts as a MP-Bus Master that is integrated into a fieldbus communications controller for local control. The fieldbus network controller communicates from a network, such as Ethernet or LonWords to bridge data to the MP-Bus Master module.
Page 11
When configuring the system, it must be ensured that this total current is not exceeded. If this should be the case, then an additional supply module must be used. The module 750-643 can be used with all WAGO-I/O-SYSTEM 750 controllers, except of the MODBUS programmable controllers 750-812/-814/-815/-816.
12 • 750-643 [MP-Bus Master Module] Indicating devices 2.1.1.3 Indicating devices Designation State Function Enable Enable Handheld not active Handheld green Enable Handheld active active 13 14 Transmission signal TxD not present green Transmission signal TxD present 24 V 24 V MP-Bus supply not present Fig.
750-643 [MP-Bus Master Module] • 13 Technical data 2.1.1.5 Technical data Module-specific data MP-Bus specification Belimo PP/MP Specifications V1.21 (valid from 1.10.2002) Maximum number of slaves Supply voltage (MP-Bus) DC 24 V via power contacts Current consumption (MP-Bus) 25 mA without motor current (for MP-Bus)
750-643 [MP-Bus Master Module] Functional description More Information Detailed references to the approvals are listed in the document "Overview Approvals WAGO-I/O-SYSTEM 750", which you can find on the CD ROM ELECTRONICC Tools and Docs (Item-No.: 0888-0412) or in the internet under: http://www.wago.com ...
2.1.1.7 Process data The bus module 750-643 makes an 8-byte process image available to the fieldbus controller via 1 logical channel. The data to be sent and received are stored in 6 output bytes (D0 ...D5) and 6 input bytes (D0 ...D5). Two control bytes (C0, C1) and two status bytes (S0, S1) are used to control the data flow.
Page 16
The IEC application can be implemented in the connected programmable fieldbus controller (PFC) of the fieldbus node with the WAGO-I/O-PRO or WAGO-CAA programming tool. WAGO-I/O-SYSTEM 750...
The byte length of pure MP/PP telegrams varies between min. 4 bytes and max. 10 bytes. The typical length is 7 bytes. The module bus communication of all WAGO-I/O-SYSTEM 750 fieldbus controllers provides a maximum of 8 bytes, including control and status bytes, in each module bus telegram. MP- Bus messages must therefore be split.
18 • 750-643 [MP-Bus Master Module] Data transfer 2.1.1.8.1 Message codes for the extended control byte MSG_CODE DPID DATA Description Null message D0-4 not used F2K_NULL D0-4 not used MP-Bus driver request for initialization D0-4 not used F2K_INIT D0-4 not used Module test (transparent communication).
750-643 [MP-Bus Master Module] • 19 Data transfer 2.1.1.8.2 Message codes for the extended status byte MSG_CODE DPID DATA Description Null message D0-4 not used K2F_NULL D0-4 not used ERR=0 MP-Bus driver initialization has been carried out. D0-4 not used...
D0-D4 not used 2.1.1.8.3 Use of the module 750-643 with programmable fieldbus controllers Appropriate IEC 61131-3 function blocks and libraries are available for WAGO-I/O-PRO 32 and WAGO-I/O-PRO CAA in order to read out the process data of the MP-Bus Master Module with a programmable fieldbus controller (PFC).
750-643 [MP-Bus Master Module] • 21 Data transfer Further information The function blocks and libraries for WAGO-I/O-PRO can be downloaded free of charge from the internet. You will find these at http://www.wago.com under the heading Building Automation Portal Downloads.
22 • 750-643 [MP-Bus Master Module] Data transfer FuRaw2Temp_NI1000_LuS Conversion Ni 1000 (Landis & Staefa) FuRaw2Temp_NTC5K Conversion NTC 5 KΩ FuRaw2Temp_PT1000 Conversion PT 1000 2.1.1.8.4 Function macros Function macros are instances, which carry out stand-alone or multiple MP- Bus communications. They are responsible for the sequential flow (transmit/receive) of MP-Bus telegrams.
750-643 [MP-Bus Master Module] • 23 Data transfer 2.1.1.8.4.2 Function macro input process data MSG_COD Description MP-Bus addressing Type 1 Start byte for the programmed device after requesting the serial number D2-4 Serial number of the programmed MP-Bus device K2F_FM...
MP master and the drives. Note The module 750-643 supplies the connected bus nodes exclusively with a DC voltage of 24 V DC. Neither a special cable nor a termination resistor is required. The MP-Bus network can therefore be made up using commercially available installation cable.
Page 25
750-643 [MP-Bus Master Module] • 25 Network structure Fig. 2.1.1-4: MP-Bus length as a function of the active power of all drives p064305x Example: Total active power of all drives: W = 10 W. tot. Diagram curve Core cross section Bus length 0.75 mm²...
26 • 750-643 [MP-Bus Master Module] Network structure 2.1.1.9.3 Bus circuit 24 V 24 V 750-643 MP-Bus DC 24 V … max. 8 MFT2 MFT2 MFT2 modules active sensor switch (ON/OFF) passive sensor active sensor switch (ON/OFF) Fig. 2.1.1-5: MP-Bus circuit g064307d Up to 8 slaves can be connected to one master.
750-643 [MP-Bus Master Module] • 27 Network structure 2.1.1.9.4 Topology There are no restrictions with regard to the network topology. Star, ring and tree structures are possible as well as mixed forms. Master Master Sensor Sensor Sensor Sensor Slave Sensor...
Page 28
28 • 750-643 [MP-Bus Master Module] Network structure If an external master is detected by the module, the MP-Bus module switches off its own master functionality, as long as the external master is active and is sending telegrams. This condition is signaled to the fieldbus controller by means of the associated status bit in the extended status byte via the module bus.