Process Data Architecture; Basic Structure - WAGO -I/O-SYSTEM 750 XTR Manual

Fc ethernet g3 xtr fieldbus coupler ethernet; 3rd generation; extreme
Hide thumbs Also See for WAGO-I/O-SYSTEM 750 XTR:
Table of Contents

Advertisement

78
Function Description
Pos : 60 /All e Seri en (Allgemei ne Module)/Ü berschriften/Ebene 2/Prozes sdatenaufbau - Ü berschrift 2 @ 5\mod_1245069543813_21.doc x @ 35310 @ 2 @ 1
7.2

Process Data Architecture

Pos : 61.1 /Serie 750 (WAGO-I/O-SYST EM)/F unktions beschr eibung/Prozes sabbild/Proz ess abbil d - Koppl er-NEU l t. Kirste @ 7\mod_1271769007509_21.doc x @ 55460 @ 3 @ 1
7.2.1

Basic Structure

After switching on the supply voltage, the fieldbus coupler identifies all I/O
modules connected with the node that send or receive data (data width/bit width
> 0). In the maximum total extension the node can consist of a mixed
arrangement of a maximum of 64 analog and digital I/O modules, connected on
the fieldbus coupler.
The data of the digital I/O modules are bit-oriented; i.e., digital data are sent bit
by bit. The data of the analog I/O modules are byte-oriented; i.e., analog data are
sent byte by byte. The term "Analog I/O modules" represents the group of byte-
oriented I/O modules, which send data byte by byte. This group includes, for
example, counter modules and angle and distance measurement modules.
The fieldbus coupler stores the process data in the process images. The fieldbus
coupler works with a process output data image (PIO) and a process input data
image (PII).
The PIO is filled of the fieldbus master with the process output data. The PII is
filled of the fieldbus coupler with the process input data.
Into the input and output process image the data of the I/O modules are stored in
the sequence of its physical position after the fieldbus coupler in the individual
process image.
First, all the byte-oriented I/O modules are stored in the process image, then the
bit-oriented I/O modules. The bits of the digital I/O modules are grouped into
bytes. If the amount of digital I/O information exceeds 8 bits, the fieldbus coupler
automatically starts a new byte.
Pos : 61.2 /Serie 750 (WAGO-I/O-SYST EM)/F unktions beschr eibung/Prozes sabbild/Ac htung: Gerätesc häden durc h falsc he Adres sierung @ 4\mod_1237796248146_21.doc x @ 28783 @ @ 1
Avoid equipment damages due to addressing errors!
To avoid equipment damages within the field range, you must consider that,
depending on the specific position of an I/O module in the fieldbus node, the
process data of all previous byte or bit-oriented modules must be taken into
account to determine its location in the process data map.
Pos : 61.3 /Serie 750 (WAGO-I/O-SYST EM)/F unktions beschr eibung/Prozes sabbild/Hi nweis : Proz ess datenanz ahl beac hten! @ 4\mod_1239027136158_21.doc x @ 30012 @ @ 1
Consider the Process Data size for each module!
Observe the number of input and output bits or bytes for the individual I/O
modules.
Pos : 61.4 /Serie 750 (WAGO-I/O-SYST EM)/F unktions beschr eibung/Prozes sabbild/Infor mation: Infor mati onen z u dem fel dbuss pezifisc hen Prozes sabbil d @ 4\mod_1239027644580_21.doc x @ 30018 @ @ 1
Manual
Version 1.3.0
WAGO-I/O-SYSTEM 750 XTR
750-352/040-000 FC ETHERNET G3 XTR

Advertisement

Table of Contents
loading

This manual is also suitable for:

750-352/040-000

Table of Contents