Constant Registers; Table 156: Register Address 0X2000; Table 157: Register Address 0X2001; Table 158: Register Address 0X2002 - WAGO -I/O-SYSTEM 750 XTR Manual

Fc ethernet g3 xtr fieldbus coupler ethernet; 3rd generation; extreme
Hide thumbs Also See for WAGO-I/O-SYSTEM 750 XTR:
Table of Contents

Advertisement

WAGO-I/O-SYSTEM 750 XTR
750-352/040-000 FC ETHERNET G3 XTR
Pos : 94.55 /Serie 750 ( WAGO-I/O-SYST EM)/Funkti onsbesc hrei bung/F eldbus kommuni kation/M ODBU S/Z ugriff auf R egister werte - Konstantenregister 0x2000 bis 0x2008 @ 3\mod_1235462025437_21.doc x @ 27639 @ 4 @ 1
11.2.5.7

Constant Registers

The following registers contain constants, which can be used to test
communication with the master:

Table 156: Register Address 0x2000

Register address 0x2000 (8192
Value
Access
Description

Table 157: Register Address 0x2001

Register address 0x2001 (8193
Value
Access
Description

Table 158: Register Address 0x2002

Register address 0x2002 (8194
Value
Access
Description

Table 159: Register Address 0x2003

Register address 0x2003 (8195
Value
Access
Description

Table 160: Register Address 0x2004

Register address 0x2004 (8196
Value
Access
Description

Table 161: Register Address 0x2005

Register address 0x2005 (8197
Value
Access
Description
)
dec
Zero, GP_ZERO
Read
Constant with zeros
)
dec
Ones, GP_ONES
Read
Constant with ones
• –1 if this is declared as "signed int"
• MAXVALUE if it is declared as "unsigned int"
)
dec
1,2,3,4, GP_1234
Read
This constant value is used to test the Intel/Motorola format specifier. If the master
reads a value of 0x1234, then with Intel format is selected – this is the correct
format. If 0x3412 appears, Motorola format is selected.
)
dec
Mask 1, GP_AAAA
Read
This constant is used to verify that all bits are accessible to the fieldbus master.
This will be used together with register 0x2004.
)
dec
Mask 1, GP_5555
Read
This constant is used to verify that all bits are accessible to the fieldbus master.
This will be used together with register 0x2003.
)
dec
Maximum positive number, GP_MAX_POS
Read
Constant in order to control arithmetic.
Fieldbus Communication 185
Version 1.3.0
Manual