28
System Description
Pos : 19.16.19 /Seri e 750 ( WAGO-I/O-SYSTEM)/Systembes chr eibung/Versorgung/Beis piel: @ 3\mod_1232630417843_21.doc x @ 26605 @ @ 1
Example:
Pos : 19.16.20 /Seri e 750 ( WAGO-I/O-SYSTEM)/Systembes chr eibung/Versorgung/Systemvers orgung - Ausl egung - Beispi el 1 (neues Gehäus e) @ 8\mod_1279035265655_21.doc x @ 59860 @ @ 1
Calculating the current consumption on an example coupler
Internal current consumption
Residual current for bus modules
Sum I
(5 V) total
Pos : 19.16.21 /Seri e 750 ( WAGO-I/O-SYSTEM)/Systembes chr eibung/Versorgung/Systemvers orgung - Ausl egung - Inter ne Stromaufnahme/Summenstr om @ 3\mod_1232950111375_21.doc x @ 26816 @ @ 1
The internal current consumption is indicated in the technical data for each bus
terminal. In order to determine the total requirement, add together the values of
all I/O modules in the node.
Please note the aggregate current for I/O modules. It may be necessary to
supply potential!
When the sum of the internal current consumption for the I/O modules exceeds
their aggregate current, you must use a supply module with bus power supply.
Install it before the position where the permissible aggregate current would be
exceeded.
Pos : 19.16.22 /Seri e 750 ( WAGO-I/O-SYSTEM)/Systembes chr eibung/Versorgung/Beis piel: @ 3\mod_1232630417843_21.doc x @ 26605 @ @ 1
Example:
Pos : 19.16.23 /Seri e 750 ( WAGO-I/O-SYSTEM)/Systembes chr eibung/Versorgung/Systemvers orgung - Ausl egung - Beispi el 2 (neues Gehäus e) @ 8\mod_1279035418672_21.doc x @ 59863 @ @ 1
Calculating the total current on the example coupler
A node with an example coupler consists e. g. of the following I/O modules:
20 relay modules (750-517) and 10 digital input modules (750-405).
Internal current consumption
Sum
In this example, the example coupler can provide 700 mA for the I/O modules.
This value is given in the associated data sheet ("Total current for I/O modules").
Consequently, an internal system supply module (750-613), e. g. in the middle of
the node, should be added.
Pos : 19.16.24 /Seri e 750 ( WAGO-I/O-SYSTEM)/Systembes chr eibung/Versorgung/Systemvers orgung - Ausl egung - Berec hnung Ei ngangsstrom XTR @ 18\mod_1392381249671_21.doc x @ 145538 @ @ 1
The maximum input current of the 24 V system supply is 500 mA. The exact
electrical consumption (I
Manual
Version 1.3.0
750-352/040-000 FC ETHERNET G3 XTR
300 mA at 5 V
700 mA at 5 V
1000 mA at 5 V
10 * 90 mA =
20 * 2 mA =
) can be determined with the following formulas:
(V)
WAGO-I/O-SYSTEM 750 XTR
900 mA
40 mA
940 mA