WAGO-I/O-SYSTEM 750 XTR
750-352/040-000 FC ETHERNET G3 XTR
In exceptional instances, I/O modules can be directly connected to the
field supply!
The 24 V field supply can be connected also directly to a bus module, if the
connection points are not needed for the peripheral device supply. In this case,
the connection points need the connection to the power jumper contacts.
Pos : 19.16.34 /Seri e 750 ( WAGO-I/O-SYSTEM)/Systembes chr eibung/Versorgung/F eldversorgung - Ans chl uss - Weiterl eitung Vers orgungsspg., Strombel astung 10 A, neues Eins peisemodul @ 8\mod_1279805441785_21.doc x @ 60845 @ @ 1
The field-side power supply is automatically derived from the power jumper
contacts when snapping an I/O module.
The current load of the power contacts must not exceed 10 A on a continual
basis.
By inserting an additional power supply module, the field supply via the power
contacts is disrupted. From there a new power supply occurs which may also
contain a new voltage potential.
Pos : 19.16.35 /Seri e 750 ( WAGO-I/O-SYSTEM)/Systembes chr eibung/Versorgung/F eldversorgung - Ans chl uss - 2 Hi nweise: Potential neu ei ns peis en + Dis tanz modul @ 3\mod_1232950091343_21.doc x @ 26724 @ @ 1
Re-establish the ground connection when the connection to the power
jumper contacts is disrupted!
Some I/O modules have no or very few power contacts (depending on the I/O
function). Due to this, the passing through of the relevant potential is disrupted. If
you require a field supply via power jumper contacts for subsequent I/O modules,
then you have to use a power supply module.
Note the data sheets of the I/O modules.
Use a spacer module when setting up a node with different potentials!
In the case of a node setup with different potentials, e.g. the alteration from
24 VDC to 230 VAC, you should use a spacer module. The optical separation of
the potentials acts as a warning to heed caution in the case of wiring and
maintenance works. Thus, you can prevent the results of wiring errors.