174 •
MODBUS Functions

MODBUS Register Mapping

6.4 MODBUS Register Mapping
The following tables display the MODBUS register mapping for the process
image, the PFC variables, the NOVRAM data, and the internal variables is
represented.

Register (Word) Access Reading:

Start address
0x0000
0x0100
0x0200
0x0300
0x1000
0x3000
0x6000
0x7000
Register (Word) Access Writing:
Start address
0x0000
0x0100
0x0200
0x0300
0x1000
0x3000
0x6000
0x7000
End
Memory range
address
0x00FF
physical Inputs process image (1)
0x01FF
Output registers of the PFC variables (MODBUS TCP)
0x02FF
physical Outputs process image (1)
0x03FF
Input registers of the PFC variables (MODBUS TCP)
0x2FFF
Internal variables (see next Chapter 6.5)
0x5FFF
NOVRAM (24 kByte) Retain range for flags
0x62FC
physical Inputs process image (2)
0x72FC
physical Outputs process image (2)
End
Memory range
address
0x00FF
physical Outputs process image (1)
0x01FF
Input registers of the PFC variables (MODBUS TCP)
0x02FF
physical Outputs process image (1)
0x03FF
Output registers of the PFC variables (MODBUS TCP)
0x2FFF
Internal variables (see next Chapter 6.5)
0x5FFF
NOVRAM (24 kByte) Retain range for flags
0x62FC
physical Outputs process image (2)
0x72FC
physical Outputs process image (2)
WAGO-I/O-SYSTEM 750
ETHERNET TCP/IP