Item
Approximate Mass
External Dimensions
Recommended Cable
2) Output Characteristics
The following diagram show the output characteristics. Two modes are available:
±2000 mode and 0-4000 mode. The mode is selected by I/O allocation.
Output register value
≤-2000
-1000
0000
+1000
+2000
+3000
≥+4000
10
5
Analog output value(V)
0
-5
-10
10
5
Analog output value(V)
0
-5
-10
Note: (1) For ±2000 mode, if output register value exceeds the range from
-2000 to +2000, the analog output value will be clamped at -
10.00 or +10.00 V.
(2) For 0-4000 mode, if output register value exceeds the range from
0 to 4000, the analog output value will be clamped at -10.00 or
+10.00 V.
350 g
40.3×130×103.9 mm (W×H×D)
Shielded twisted-pair wires
2
1.3 mm
(AWG16) to 0.5 mm
Analog output value
±2000 mode
-10.00 V
-5.00 V
0.00 V
+5.00 V
+10.00 V
+10.00 V
+10.00 V
-2000
-1000
+2000 mode
0
1000
0-4000 mode
4-21
4.2 Analog Output Specifications
Specification
2
(AWG20)
0-4000 mode
-10.00 V
-10.00 V
-10.00 V
-5.00 V
0.00 V
+5.00 V
+10.00 V
0
1000
2000
Output register value
2000
3000
4000
Output register value
4