2) The following diagram shows the circuit configuration.
From CPU
If using a 12/24-VDC 16-point Output Module (sourcing), connect a fuse, which
CAUTION
complies with the load specifications, in series with the load.
A protective fuse built into the following 12/24-VDC 16-point Output Modules
does not protect the output element. If a fuse is not connected, a fire or dam-
age to the devices or output circuits may occur if the load is short-circuited or
the circuit overloaded.
Output signal
indicator
Photocoupler
Blown fuse/
Power disconnected
indicator
Blown-fuse
Fuse
detection circuit
3-41
3.2 Digital Output Module Specifications
Loads
Output 1
Output 8
- Common 1
+ Common 1
12/24 VDC
Output 9
Loads
Output 16
- Common 2
+ Common 2
12/24 VDC