Relay Contact 16-Point Output Module - YASKAWA MEMOCON GL120 User Manual

Table of Contents

Advertisement

3.2.8

Relay Contact 16-point Output Module

1) Performance Specifications
Item
Name
Model Name
Model No.
Rated Voltage/Current
Maximum Load Power
Maximum Load Voltage
Minimum Load
Voltage/Current
Contact Resistance
Contact Life
Output Delay Times
Output Type
Number of Commons
Number of Outputs per Common
Output Power Supply per
Common
External Connections
Output Protection Type
Built-in Fuse
Surge Suppressor
Other Output Protection
Number of Outputs
Output Signal Indication
Status Indication
Insulation Method
Dielectric Strength
Insulation Resistance
External Power Supply
Derating Conditions
Internal Current Consumption

Relay Contact 16-point Output Module

RELAY-16P
JAMSC-120DRA84300
200 VAC, 1 A, resistive load
24 VDC, 1 A, resistive load
750 VA (AC loads)
90W (DC loads)
264 VAC/125 VDC
100 mVDC, 0.1 mA
100 mΩ max.
Electrical
3 A at 30 VDC, resistive load: 100,000 operations min.
1 A at 30 VDC, resistive load:
1 A at 120 VAC, cosφ = 1.0:
1 A at 240 VAC, cosφ = 1.0:
Mechanical
20 million operations min.
OFF to ON: 10 ms max.
ON to OFF: 15 ms max.
Relay contact outputs
2
8 points/common
Connect power supplies of the same phase to the Common 1
and Common 2 for 100/200VAC.
Removable terminal block with M3 screw terminals
Unprotected outputs (according to JIS B3502)
None
None
None
16
Indicator for each point; lit when the output is ON.
Status saved in internal logic.
ACTIVE: Lights during output processing
Relay
1,500 VAC for 1 min or 1,800 VAC for 1 s between output termi-
nals and internal circuits and between all output commons
100 MΩ min. at room temperature and humidity between output
terminals and ground (measured with a 500-VDC test voltage
megohmmeter).
100/200 VAC or 24 VDC supplied to drive loads
None
610 mA max. at 5 VDC (with all points ON)
3-55
3.2 Digital Output Module Specifications
Specifications
300,000 operations min.
τ = 7 ms:
150,000 operations min.
τ = 40 ms:
40,000 operations min.
400,000 operations min.
cosφ = 0.4:
250,000 operations min.
300,000 operations min.
cosφ = 0.4:
200,000 operations min.
3