Item
Insulation Resistance
External Power Supply
Derating Conditions
Internal Current Consumption
Maximum Heating Value
Hot Swapping
(Removal/insertion under power)
Approx. Mass
External Dimensions
2) The following diagram shows the circuit configuration.
From CPU
If using a 100/200-VAC 8-point Output Module, connect a fuse, which complies with
CAUTION
the load specifications, in series with the load.
A protective fuse does not built into the following 100/200-VAC 8-point Output
Modules. If a fuse is not connected, fire or damage to the devices or output cir-
cuits may occur if the load is short-circuited or the circuit overloaded.
Specifications
100 MΩ min. at room temperature and humidity between input termi-
nals and ground
(measured with a 500-VDC test voltage megohmmeter).
100/200 VAC supplied to drive loads
None
50 mA max. at 5 VDC (with all points ON)
9.0 W
Permitted
300 g
40.3×130×103.9 mm (W×H×D)
Output signal
indicator
Phototriac
3-25
3.2 Digital Output Module Specifications
Output 1
100/200 VAC
Output 8
100/200 VAC
3