YASKAWA MEMOCON GL120 User Manual page 81

Table of Contents

Advertisement

(Continued from previous page)
Photocoupler
From CPU
If using a 12/24-VDC 64-point Output Module, connect a fuse, which complies with
CAUTION
the load specifications, in series with the load.
A protective fuse built into the following 12/24-VDC 64-point Output Modules
does not protect the output element. If a fuse is not connected, a fire or dam-
age to the devices or output circuits may occur if the load is short-circuited or
the circuit overloaded.
CN2 connector
pin numbers
Output signal
indicator
Fuse
Blown fuse/power
disconnection indi-
cator
Blown-fuse
detection circuit
3-51
3.2 Digital Output Module Specifications
Output 33
Loads
Output 34
Output 47
Output 48
- Common 3
12/24 VDC
+ Common 3
Loads
Output 49
Output 50
Output 63
Output 64
- Common 4
12/24 VDC
+ Common 4
3