3 Digital I/O Specifications
3.1.4 12/24-VDC 32-point Input Module
3) The following diagram shows an example or terminal connections.
EXAMPLE
Pin No.
12/24 VDC
12/24 VDC
Note: (1) Pins 9 and 29, pins 19 and 39 are internally connected.
Connect these pins externally as well. Not connecting
them can cause malfunction.
(2) Connectors for External Connections
On the Module: 10240-52A2JL (manufactured by 3M)
(3) Recommended wires
Use wires of 0.08mm
the connector.
(4) The polarity of the external power supply for signals can be
connected with either plus or minus.
(5) Pins 10, 20, 30, and 40 are not connected.
(6) External Connection Cable
Use a 32-point I/O Module Cable to connect to field
devices. Refer to 3.3 I/O Module Cables for details.
3-16
Pin No.
Not
Not
connected
connected
Common 2
Input 32
Input 31
Input 30
Input 29
Input 28
Input 27
Input 26
Input 25
Input 24
Input 23
Input 22
Input 21
Input 20
Input 19
Input 18
Input 17
Not
Not
connected
connected
Common 1
Input 15
Input 16
Input 13
Input 14
Input 11
Input 12
Input 9
Input 10
Input 7
Input 8
Input 5
Input 6
Input 3
Input 4
Input 1
Input 2
2
(AWG28) to connect to each pin of