YASKAWA MEMOCON GL120 User Manual page 191

Table of Contents

Advertisement

4 Analog I/O Specifications
4.4.3 I/O Allocations
2) Setting the Module Type
• Software Filter (No filter/Ave 3 times/Ave 5 times)
Note: This item is to be set only for Analog Input Modules.
• Timeout Output (Open/Hold/Set by user)
Note: This item is to be set only for Analog Output Modules.
Set the Module Type in the following procedure.
(1) Start the MEMOSOFT and select Online from the Mode Menu.
Fig. 4.5 Mode Selection: Online
I/O allocations cannot be performed while the CPU Module is in RUN status. If
necessary, stop the CPU Module. Refer to 6.1 PLC Operations in the
MEMOSOFT User's Manual (Manual number SIEZ-C825-60.10) for the proce-
dure to stop the CPU Module.
(2) Press the F2 (Config) Key to access the PLC System Configuration Screen.
f 2
Fig. 4.6 PLC System Configuration Screen
4-44