Input signal
Input signals
When allocating input registers, the MEMOSOFT is set by default to "LSB."
When input register allocation is set to "LSB," bit 15 (MSB) of the input register is
IMPORTANT
allocated to the smallest input number (input 1) on the Input Module.
b) Input Data Type
If an input register is set as the I/O reference number, data input can be set to binary
(BIN) or BCD. The MEMOSOFT is set by default to "BIN."
c) Service Scan: Normal/High-speed
Two types of service scans are available: normal and high-speed. A service scan
is recommended when using the high-speed segment function. The I/O Module is
activated before the ladder decoding of the high-speed segments. The I/Os that are
processed in synchronization with the high-speed scan are called High-speed Seg-
ment I/Os. The MEMOSOFT is set by default to "NORMAL."
CN1 pin number
Input 1
Input 2
Input 3
Input 14
Input 15
Input 16
Input 17
Input 18
Input 19
Input 30
Input 31
Input 32
CN2 pin number
Input 33
Input 34
Input 35
Input 46
Input 47
Input 48
Input 49
Input 50
Input 51
Input 62
Input 63
Input 64
Fig. 3.6 Allocation of Input Registers
3-91
LSB Setting
MSB Setting
3.4 I/O Allocation