3) Maximum Load Current for 12/24-VDC 16-point Output Modules
Although a 0.5-A load can be connected to each output point for the DC 16-point
CAUTION
Output Module, the total load must be 1.0 A or less for each of the four output points in
the same area marked by the shaded portion in the following figure. Keep the load
distribution within the 1.0-A limit.
If this limit is exceeded, damage may occur to the output circuit.
1.0 A/4 points
Fig. 6.28 Maximum Load Current for 16-point Output Modules
12 VDC
(24 VDC)
Output 1
Output 2
Output 3
Output 4
Output 5
Output 6
Output 7
Output 8
Fuse
-Common 1
+Common 1
6-47
6.4 Precautions on Wiring
0.5 A/point
Loads
Loads