3) The following illustration shows an example of terminal connections with AC loads.
EXAMPLE
Output 1
Output 2
Output 3
Output 4
Output 5
Output 6
Output 7
Output 8
Common 1
Not connected.
Output 9
Output 10
Output 11
Output 12
Output 13
Output 14
Output 15
Output 16
Common 2
Not connected.
If using a single-phase 100/200-VAC power supply for driving loads of the Relay
CAUTION
Contact Output Module, connect a power supply of the same phase to the Common 1
and Common 2 of the Relay Contact Output Module.
If power supplies of different phases are connected, overheating or fire may
result.
If using a Relay Contact Output Module, connect a fuse, which complies with the load
CAUTION
specifications, in series with the load.
A protective fuse does not built into the following Relay Contact Output Mod-
ules. If a fuse is not connected, fire or damage to the devices or output circuits
may occur if the load is short-circuited or the circuit overloaded.
Note: (1) Crimp Terminals
Use M3 terminals for crimping to the terminal block.
(2) Recommended Wires
Use wires of 1.3 mm
block. Use cables of the size more than 1.3 mm
(3) Terminal 10 and terminal 20 are not connected.
Terminals
2
2
(AWG16) to 0.5 mm
(AWG20) to connect to the terminal
2
3-57
3.2 Digital Output Module Specifications
Loads
Loads
100/200 VAC
(AWG16) for common lines.
3