4 Analog I/O Specifications

4.1.2 Analog Input Modules (0 to 10 V, 4 channels)

4.1.2
1) Performance Specifications

Analog Input Modules (0 to 10 V, 4 channels)

Item
Name
Model Name
Model No.
Input Signal Range
Number of Input Channels
Input Impedance
Maximum Allowable Overload
Digital Resolution
Data Format
Error
Input Delay Time
Sampling Interval
Input Filter Characteristics
Number of Allocated Words
Maintenance/Diagnosis Functions
External Connections
Status Indication
Insulation Method
Dielectric Strength
Insulation Resistance
External Power Supply
Internal Current Consumption
Maximum Heating Value
Hot Swapping
Approximate Mass
External Dimensions
Recommended Cable
Analog Input Module (0 to 10 V, 4 CH)
A/D 0-10 V 4CH
JAMSC-120AVI02100
0 to 10 V
4 channels, isolated in common
1 MΩ min
-25 to 25 V
12 bits
Binary: 0 to +4000
±0.5% F.S. (25 °C)
±1.0% F.S. (0 to 60 °C)
4 ms max.
Input data is renewed for every scan by CPU
3 ms max.
5 words/Module
Watchdog timer (timeout: 262 ms)
Removable terminal block with M3 screw terminals
RDY: Lights when Module is normal
ACT: Lights during input processing
ERR: Lights when overrange is detected
CH1 to CH4: The corresponding LED is lit when overrange is
detected for the channel.
Overrange: +10.12 V < channel input signal
Photocoupler
1,500 VAC for one minute between input terminals (con-
nected together) and internal circuits
No insulation between input channels
100 MΩ min. at room temperature and humidity between
input terminals and ground (measured with a 500-VDC test
voltage megohmmeter).
Not needed
450 mA max. at 5 VDC
2.3 W
Permitted
300 g
40.3×130×103.9 mm (W×H×D)
Shielded twisted-pair wires
2
1.3 mm
(AWG16) to 0.5 mm
4-8
Specification
2
(AWG20)