2) Input Characteristics
The following diagram show the input characteristics.
Analog Input Value
≤0.00 V
2.50 V
5.00 V
7.50 V
10.00 V
≥10.12 V
Input register value
Note: Input values exceeding the range of 0.00 V to 10.12 V will be
clamped at 0 or 4048.
Input Register Value
0000
1000
2000
3000
4000
4048
0-4000 mode
Analog input value (V)
4-9
4.1 Analog Input Specifications
4