YASKAWA MEMOCON GL120 User Manual page 209

Table of Contents

Advertisement

3) I/O Reference Number Setting
The following table shows the I/O reference numbers and points that can be allo-
cated.
Type of Input
CPU10, CPU20, CPU21
Input registers
30001 to 300512
4) Parameter Setting
a) Service Scan: Normal/High-speed
Two types of service scans are available: normal and high-speed. A service scan
is recommended when using the high-speed segment function. The I/O module is
activated before the ladder decoding of the high-speed segments. The I/Os that are
processed in synchronization with the high-speed scan are called High-speed Seg-
ment I/Os. The MEMOSOFT is set by default to "NORMAL."
b) Mode
The number of data input from the Register Input Module can be set.
Either 8CH or 16CH can be set.
The MEMOSOFT is set by default to "16CH."
c) Cycle
The reading cycle of input data can be set.
Any of six cycles listed in the following table can be set according to the set mode.
Mode
Cycle
The MEMOSOFT is set by default to 32/64 ms.
When a specified value is set for the cycle, the values of Timing T1 and T2 are set
according to the set cycle.
The following table shows the values of Select Timings when a specified value is
selected for the cycle.
Table 5.2 Select Timing When a Specified Value is Selected for Cycle
Mode
8CH
10 ms
32 ms
64 ms
192 ms
320 ms
References for I/O Allocation
CPU30, CPU35
300001 to 300512
Table 5.1 Cycles
8CH
10 ms
32 ms
64 ms
192 ms
320 ms
User set
16CH
20 ms
64 ms
128 ms
384 ms
640 ms
5-11
5.3 I/O Allocation
Number of Registers
1 to 16 registers
16CH
20 ms
64 ms
128 ms
384 ms
640 ms
User set
Timing
T1
T2
0.9 ms
0.4 ms
3.5 ms
0.5 ms
7.0 ms
1.0 ms
21.0 ms
3.0 ms
35.0 ms
5.0 ms
5

Advertisement

Table of Contents
loading

This manual is also suitable for:

Memocon gl130

Table of Contents