8 EN Standard Low voltage Directive Compliant I/O Modules
8.1.4 Specifications of the I/O Modules
2) 200- to 240-VAC 16-point Input Modules
Name
Model Name
Model No.
Rated Voltage
Maximum Allowable Voltage
Rated Frequency
Allowable Frequency Range
Inrush Current
Rated Current
Input Impedance
Standard Operating Ranges
Input Type
Input Delay Times
Number of Commons
Number of Inputs per Common
Input Power Supply per Common
External Connections
Number of Inputs
Input Signal Indication
Status Indication
Insulation Method
Dielectric Strength
Insulation Resistance
External Power Supply
Derating Conditions
Internal Current Consumption
Hot Swapping (Removal/insertion
under power)
Maximum Heating Value
Approximate Mass
External Dimensions
Table 8.3 Specifications of 200- to 240-VAC 16-point Input Modules
Item
200- to 240-VAC 16-point Input Module
AC200IN-16P
JAMSC-120DAI74309 (EN standard)
200 to 240 VAC
264 VAC
50/60 Hz
47 to 63 Hz
320 mA
7 mA (at 200 VAC, 50 Hz)
28.6 kΩ (at 200 VAC, 50 Hz)
23.1 kΩ (at 200 VAC, 60 Hz)
ON voltage range: 159 to 264 VAC
OFF voltage range: 40 VAC max.
AC type 2 (according to IEC 1131-2)
OFF to ON: 20 ms max.
ON to OFF: 35 ms max.
2
8 points/common
Connect power supplies of the same phases to the common 1 and
common 2.
Removable terminal block with M3 screw terminals.
16
Indicator for each point; lit when the input is ON.
Status saved in internal logic
ACTIVE: Lit during input processing
Photocoupler
1,500 VAC for 1 min. or 1,800 VAC for 1 s between input terminals
and internal circuits and between all input commons
100 MΩ min. at room temperature and humidity between input ter-
minals and ground (measure by a 500-VDC test voltage megohm-
meter)
200 to 240 VAC supplied to signals
None
90 mA max. at 5 VDC (with all points ON)
Permitted
3.5 W
250 g
40.3×130×103.9 mm (W×H×D)
Specifications
8-8