YASKAWA MEMOCON GL120 User Manual page 298

Table of Contents

Advertisement

5) Relay Contact 16-point Output Modules
Table 8.6 Specifications of Relay Contact 16-point Output Modules
Item
Name
Model Name
Model No.
Rated Voltage/Current
Maximum Load Power
Maximum Load Voltage
Minimum Load Voltage/Current 100 mVDC, 0.1 mA
Contact Resistance
Contact
Electrical
Life
Mechanical
Output Delay Times
Output Type
Number of Commons
Number of Outputs per Common
Output Power Supply per Common
External Connections
Output Protection Type
Builtñin Fuse
Surge Suppressor
Other Output Protection
Number of Outputs
Output Signal Indication
Status Indication
Insulation Method
Dielectric Strength
Insulation Resistance
External Power Supply
Derating Conditions
8.1 EN Standard Compliant I/O Modules
Specification
Relay Contact 16-point Output Module
RELAY-16P
JAMSC-120DRA84309 (EN standard)
240 VAC, 1 A, resistive load
24 VDC, 1 A, resistive load
750 VA (AC loads)
90 W (DC loads)
264 VAC/125 VDC
100 mΩ max.
3 A at 30 VDC, resistive load:100,000 operations min.
1 A at 30 VDC, resistive load: 300,000 operations min.
τ = 7 ms:
τ = 40 ms:
1 A at 120 VAC, cosφ = 1.0:
cosφ = 0.4:
1 A at 240 VAC, cosφ = 1.0:
cosφ = 0.4:
20 million operations min.
OFF to ON: 10 ms max.
ON to OFF: 15 ms max.
Relay contact outputs
2
8 points/common
a) When using an AC power supply (100 to 120 VAC or 200 to
240 VAC), connect Power supplies with the same phase to
the common 1 and common 2.
b) Do not connect AC power supply and DC power supply to
one common.
Removable terminal block with M3 screw terminals
Unprotected outputs (according to IEC1131-2)
None
None
None
16
Indicator for each point; lit when the output is ON.
Status saved in internal logic.
ACTIVE: Lit during output processing
Relay
1,500 VAC for 1 min or 1,800 VAC for 1 s between output termi-
nals and internal circuits and between all output commons
100 MΩ min. at room temperature and humidity between out-
put terminals and ground (measured by a 500-VDC test voltage
megohmmter)
100 to 120-VAC or 200 to 240-VAC or 24 VDC supplied to drive
loads
None
8-11
150,000 operations min.
40,000 operations min.
400,000 operations min.
250,000 operations min.
300,000 operations min.
200,000 operations min.
8