(2) A screen will appear so that the software filter setting can be selected.
Move the cursor to NO FILTER, AVE 3 TIMES or AVE 5 TIMES and press the
Enter Key to select the desired software filter.
The MEMOSOFT is set by default to NO FILTER.
The software filter selection is only for Analog Input Modules, but not for Analog
INFO
Output Modules.
7) Setting the Timeout Output (Only for Analog Output Modules)
Make sure that the Parameter Setting Screen (I/O Map Module Editor) is being dis-
played.
(1) Move the cursor to OUT STATUS WHEN CPU STOP and press the Enter Key
to access the timeout output setting.
(2) A screen will appear so that the timeout output setting can be selected.
Move the cursor to OPEN OUTPUT, HOLD OUTPUT or SET BY USER and
press the Enter Key to select the desired timeout output status. If HOLD OUT-
PUT is selected, the data just before the CPU Module entered STOP status will
be sent for all outputs until the CPU Module returns to RUN status.
Fig. 4.18 Software Filter Selection
Fig. 4.19 Parameter Setting Screen: Timeout Output
4-49
4.4 Operations Using MEMOSOFT