YASKAWA MEMOCON GL120 User Manual page 27

Table of Contents

Advertisement

3) Digital Output Modules
a) Function
b) Specifications
Name
Model
Model No.
Name
100/200-
ACOUT
JAMSC-
VAC
-8P
120DAO83
8-point
000
Output
Module
100/200-
ACOUT
JAMSC-
VAC
-16P
120DAO84
16-point
300
Output
Module
12/24-VDC
DC24O
JAMSC-
8-point
UT-8P
120DDO33
Output
000
Module
12/24-VDC
DC24O
JAMSC-
16-point
UT-
120DDO34
Output
16PSN
310
Module
(sinking)
12/24-VDC
DC24O
JAMSC-
16-point
UT-
120DDO34
Output
16PSR
320
Module
(sourcing)
12/24-VDC
DC24O
JAMSC-
32-point
UT-
120DDO35
Output
32PSN
410
Module
(sinking)
12/24-VDC
DC24O
JAMSC-
64-point
UT-
120DDO36
Output
64PSN
410
Module
(sinking)
Relay con-
RELAY-
JAMSC-
tact
16P
120DRA84
16-point
300
Output
Module
A Digital Output Module converts the numeric data stored in output registers or the
ON/OFF state of the output coil in the state memory of the CPU Module into digital
signals for control of indicators, electromagnetic switches, relays, solenoid valves,
numeric indicators, etc.
The following table shows the main specifications of Digital Output Modules.
Table 2.5 Main Specifications of Digital Output Modules
Rated
Load
Remarks
Volt-
Current
age
100/
1.0 A/
Unpro-
200
point
tected
VAC
outputs
100/
0.6 A/
Unpro-
200
point
tected
VAC
outputs
12/24
2.0 A/
Short-cir-
VDC
point
cuit pro-
tection
Sourcing/
sinking
outputs
12/24
0.5 A/
Unpro-
VDC
point,
tected
1.0 A/
outputs
4 points
Sinking
outputs
12/24
0.5 A/
Unpro-
VDC
point,
tected
1.0 A/
outputs
4 points
Sourcing
outputs
12/24
0.3 A/
Unpro-
VDC
point,
tected
0.4 A/
outputs
4 points
Sinking
outputs
12/24
0.1 A/
Unpro-
VDC
point
tected
output
Sinking
outputs
Relay
1.0 A/
Unpro-
contact
point
tected
outputs
Output
Num
ber
Delay
of
Times
Out-
puts
OFF→ON:
8
Max. 5 ms
ON→OFF:
1/2 cycle +
5 ms max.
OFF→ON:
16
Max. 5 ms
ON→OFF:
1/2 cycle +
5 ms max.
OFF→ON:
8
Max. 3 ms
ON→OFF:
Max. 5 ms
OFF→ON:
16
Max. 1 ms
ON→OFF:
Max. 1 ms
OFF→ON:
16
Max. 1 ms
ON→OFF:
Max. 1 ms
OFF→ON:
32
Max. 1 ms
ON→OFF:
Max. 1 ms
OFF→ON:
64
Max. 1 ms
ON→OFF:
Max. 1 ms
OFF→ON:
16
Max. 10 ms
ON→OFF:
Max. 15 ms
2-7
2.2 I/O Modules
Internal
Maxi-
Hot
mum
Current Con-
Swap
Heat-
sumption
ping
ing
Value
With all
9.0 W
Per-
points ON:
mit-
150 mA
ted
With all
5.5 W
Per-
points ON:
mit-
300 mA
ted
With all
1.6 W
Per-
points ON:
mit-
220 mA
ted
With all
7.1 W
Per-
points ON:
mit-
220 mA
ted
With all
7.5 W
Per-
points ON:
mit-
300 mA
ted
With all
6.5 W
Per-
points ON:
mit-
330 mA
ted
With all
13.0 W Per-
points ON:
mit-
650 mA
ted
With all
3.1 W
Per-
points ON:
mit-
610 mA
ted
2