Although the capacity of the surge absorber used must be adjusted to the load, the
following surge absorber is recommended for general applications:
• CR50500 (manufactured by Okaya Electric Industries Co., Ltd.) or equivalent.
Fig. 6.15 Connecting Contacts to an Inductive Load
4) Maximum Load Current
Although a 0.6-A load can be connected to each output point for AC 16-point Output
CAUTION
Module, the total load must be 2.4 A or less for each common. Keep the maximum
load at 2.4-A for each common.
If this limit is exceeded, damage may occur to the output circuit.
2.4 A/common
Fig. 6.16 Maximum Load Current
100 VAC
(200 VAC)
Output
Output
Common
1-1
Common
1-2
Fuse
Common 1-1
6-37
6.4 Precautions on Wiring
Surge absorber
Inductive
load
Load
100 VAC
(200 VAC)
Loads
Fuses
Output 1
Output 2
Output 3
Output 4
Output 5
Output 6
Output 7
Output 8
Common 1-2
6
0.6 A/point