YASKAWA MEMOCON GL120 User Manual page 88

Table of Contents

Advertisement

3 Digital I/O Specifications
3.2.8 Relay Contact 16-point Output Module
4) The following diagram shows an example of terminal connections with DC loads.
EXAMPLE
CAUTION
Note: (1) Crimp Terminals
(2) Recommended Wires
(3) Terminal 10 and terminal 20 are not connected.
Terminals
Output 1
Output 2
Output 3
Output 4
Output 5
Output 6
Output 7
Output 8
Common 1
Not connected.
Output 9
Output 10
Output 11
Output 12
Output 13
Output 14
Output 15
Output 16
Common 2
Not connected.
If using a Relay Contact Output Module, connect a fuse, which complies with the load
specifications, in series with the load.
A protective fuse does not built into the following Relay Contact Output Mod-
ules. If a fuse is not connected, fire or damage to the devices or output circuits
may occur if the load is short-circuited or the circuit overloaded.
Use M3 terminals for crimping to the terminal block.
2
Use wires of 0.8 mm
(AWG18) to 0.2 mm
block.
12/24 VDC
12/24 VDC
2
(AWG24) to connect to the terminal
3-58
Loads
Loads

Advertisement

Table of Contents
loading

This manual is also suitable for:

Memocon gl130

Table of Contents