5 Register I/O Specifications

5.2.1 Register Output Modules

5.2

Register Output Specifications

5.2.1
1) Performance Specifications
Name
Model Name
Model No.
Rated Voltage
Allowable Voltage Range
Output Form
Maximum Load Current
Output Voltage Drop
Output Delay Time
OFF Leakage Current
Output Type
Output Protection Type
Built-in Fuse
Surge suppressor
Other Output Protections
Number of Outputs
Output Signal Indication
External Connections
Status Indication
Insulation Method
Dielectric Strength
Insulation Resistance
External Power Supply
Derating Conditions
Internal Current Consumption
This section describes performance specifications, circuit configuration, external
connections, and appearance of the 120-series Register Output Modules.

5.2.1 Register Output Modules - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 5-6

Register Output Modules
Item
Specifications
Register Output Module
REGISTER-OUT
JAMSC-120RDO34410
12/24 VDC
10.2 to 30.0 VDC
Sinking output
Data output circuit: 100 mA per point, 800 mA per 16 points
Select output circuit: 100 mA per point
1.5V (0.1A) max.
OFF to ON: 1 ms max.
ON to OFF: 1 ms max.
1 mA max. (24 VDC)
Transistor output
Data output circuit: Protected output (according to JIS B 3502)
Select output circuit: Unprotected output
(according to JIS B 3502)
One 1-A fuse
(Blowout time: Two minute max. at 200 % of rated current)
None
None
Data output circuit: 16 points
Select output circuit: 16 points
None
40-pin connector: one piece
Connector type: FCN-365P040 (made by Fujitsu Ltd.)
R: Lights while the Module is operating normally.
ACTIVE: Lights during output processing
F: Lights when the fuse is blown out or the output power supply
is disconnected.
Photocoupler
1,500 VAC for 1 min or 1,800 VAC for 1 s between the output
terminals (connected together) and the internal circuits.
100 MΩ min. at room temperature and humidity between the
output terminals and the ground (measured with a 500 VDC
test voltage megohmmeter).
12/24 VDC supplied to drive loads
None
400 mA max. at 5 VDC
5-6