3 Digital I/O Specifications

3.2.3 12/24-VDC 8-point Output Module

3.2.3
1) Performance Specifications

12/24-VDC 8-point Output Module

Item
Name
Model Name
Model No.
Rated Voltage
Allowable Voltage Range
Output Form
Maximum Load Current
Output Voltage Drop
Output Delay Times
OFF Leakage Current
Output Type
Number of Commons
External Connections
Output Protection Type
Built-in Fuse
Surge Suppressor
Other Output Protection
Number of Outputs
Output Signal Indication
Status Indication
Insulation Method
Dielectric Strength
Insulation Resistance
External Power Supply
Derating Conditions
Internal Current Consumption
Maximum Heating Value
Hot Swapping
(Removal/insertion under power)
Approximate Mass
External Dimensions
12/24-VDC 8-point Output Module
DC24OUT-8P
JAMSC-120DDO33000
12/24 VDC
10.2 to 30.0 VDC
Sourcing or sinking
2.0 A/point
0.1 V max (2.0 A)
OFF to ON: 3 ms max.
ON to OFF: 5 ms max.
1 mA max. at 24 VDC
Transistor (FET) outputs
8 (Each output circuit is independent.)
Removable terminal block with M3 screw terminals
Protected outputs (according to JIS B3502)
Eight, 3.5-A fuses (one per circuit)
(Burnout time: 1 s max. at 200% of rated current)
Zener diode
None
8
Indicator for each point; lit when the output is ON.
Status saved in internal logic.
ACTIVE: Lights during output processing.
Photocoupler
1,500 VAC for 1 min or 1,800 VAC for 1 s between output
terminals and internal circuits
100 MΩ min. at room temperature and humidity between
output terminals (connected together) and ground
(measured with a 500-VDC test voltage megohmmeter).
12/24 VDC supplied to drive loads
None
220 mA max. at 5 VDC (with all points ON)
1.6 W
Permitted
250 g
40.3×130×103.9 mm (W×H×D)